Breaker Size worksheet

Grades 6–7 · CCSS 7.RP.A.3

Solve each problem and show your work. Round answers to 2 decimal places where needed.

  1. Problem 1.
    • Load given in: Watts
    • Continuous load (runs 3 hours or more): 1,500 W
    • Noncontinuous load: 0 W
    • Circuit voltage: 125 V
    • Breaker and enclosure are listed for 100% continuous operation: No

    Find: Standard breaker size

  2. Problem 2.
    • Load given in: Watts
    • Continuous load (runs 3 hours or more): 1,300 W
    • Noncontinuous load: 0 W
    • Circuit voltage: 96 V
    • Breaker and enclosure are listed for 100% continuous operation: No

    Find: Standard breaker size

  3. Problem 3.
    • Load given in: Amps
    • Continuous load (runs 3 hours or more): 15 A
    • Noncontinuous load: 0 A
    • Breaker and enclosure are listed for 100% continuous operation: No

    Find: Standard breaker size

  4. Problem 4.
    • Load given in: Amps
    • Continuous load (runs 3 hours or more): 17 A
    • Noncontinuous load: 0 A
    • Breaker and enclosure are listed for 100% continuous operation: No

    Find: Standard breaker size

  5. Problem 5.
    • Load given in: Watts
    • Continuous load (runs 3 hours or more): 1,500 W
    • Noncontinuous load: 0 W
    • Circuit voltage: 155 V
    • Breaker and enclosure are listed for 100% continuous operation: No

    Find: Standard breaker size

  6. Problem 6.
    • Load given in: Watts
    • Continuous load (runs 3 hours or more): 1,200 W
    • Noncontinuous load: 0 W
    • Circuit voltage: 120 V
    • Breaker and enclosure are listed for 100% continuous operation: No

    Find: Standard breaker size

  7. Problem 7.
    • Load given in: Amps
    • Continuous load (runs 3 hours or more): 16 A
    • Noncontinuous load: 0 A
    • Breaker and enclosure are listed for 100% continuous operation: No

    Find: Standard breaker size

  8. Problem 8.
    • Load given in: Watts
    • Continuous load (runs 3 hours or more): 1,500 W
    • Noncontinuous load: 0 W
    • Circuit voltage: 180 V
    • Breaker and enclosure are listed for 100% continuous operation: No

    Find: Standard breaker size

  9. Problem 9.
    • Load given in: Watts
    • Continuous load (runs 3 hours or more): 1,300 W
    • Noncontinuous load: 0 W
    • Circuit voltage: 130 V
    • Breaker and enclosure are listed for 100% continuous operation: No

    Find: Standard breaker size

  10. Problem 10.
    • Load given in: Watts
    • Continuous load (runs 3 hours or more): 1,700 W
    • Noncontinuous load: 0 W
    • Circuit voltage: 120 V
    • Breaker and enclosure are listed for 100% continuous operation: No

    Find: Standard breaker size

Answer key: Breaker Size worksheet

  1. 1. Standard breaker size: 15 A

    1. Turn the long-running load into amps (current) by dividing watts by volts

      1,500125=12 A
    2. Do the same for the shorter-running load

      0125=0 A
    3. Count long-running loads at 125%, as NEC 210.20(A) requires, then add the rest. This is the smallest rating allowed

      0+1.25×12=15 A
    4. Breakers only come in set sizes, so pick the first one at or above that minimum (NEC 240.6(A))

      smallest standard size ≥ 15 A is 15 A
    5. See how much long-running load this breaker may carry: its rating ÷ 1.25

      151.25=12 A
    6. Check how much of the breaker's rating your total load uses

      1215×100=80%
  2. 2. Standard breaker size: 20 A

    1. Turn the long-running load into amps (current) by dividing watts by volts

      1,30096=13.5417 A
    2. Do the same for the shorter-running load

      096=0 A
    3. Count long-running loads at 125%, as NEC 210.20(A) requires, then add the rest. This is the smallest rating allowed

      0+1.25×13.5417=16.9271 A
    4. Breakers only come in set sizes, so pick the first one at or above that minimum (NEC 240.6(A))

      smallest standard size ≥ 16.9271 A is 20 A
    5. See how much long-running load this breaker may carry: its rating ÷ 1.25

      201.25=16 A
    6. Check how much of the breaker's rating your total load uses

      13.541720×100=67.71%
  3. 3. Standard breaker size: 20 A

    1. Count long-running loads at 125%, as NEC 210.20(A) requires, then add the rest. This is the smallest rating allowed

      0+1.25×15=18.75 A
    2. Breakers only come in set sizes, so pick the first one at or above that minimum (NEC 240.6(A))

      smallest standard size ≥ 18.75 A is 20 A
    3. See how much long-running load this breaker may carry: its rating ÷ 1.25

      201.25=16 A
    4. Check how much of the breaker's rating your total load uses

      1520×100=75%
  4. 4. Standard breaker size: 25 A

    1. Count long-running loads at 125%, as NEC 210.20(A) requires, then add the rest. This is the smallest rating allowed

      0+1.25×17=21.25 A
    2. Breakers only come in set sizes, so pick the first one at or above that minimum (NEC 240.6(A))

      smallest standard size ≥ 21.25 A is 25 A
    3. See how much long-running load this breaker may carry: its rating ÷ 1.25

      251.25=20 A
    4. Check how much of the breaker's rating your total load uses

      1725×100=68%
  5. 5. Standard breaker size: 15 A

    1. Turn the long-running load into amps (current) by dividing watts by volts

      1,500155=9.6774 A
    2. Do the same for the shorter-running load

      0155=0 A
    3. Count long-running loads at 125%, as NEC 210.20(A) requires, then add the rest. This is the smallest rating allowed

      0+1.25×9.6774=12.0968 A
    4. Breakers only come in set sizes, so pick the first one at or above that minimum (NEC 240.6(A))

      smallest standard size ≥ 12.0968 A is 15 A
    5. See how much long-running load this breaker may carry: its rating ÷ 1.25

      151.25=12 A
    6. Check how much of the breaker's rating your total load uses

      9.677415×100=64.52%
  6. 6. Standard breaker size: 15 A

    1. Turn the long-running load into amps (current) by dividing watts by volts

      1,200120=10 A
    2. Do the same for the shorter-running load

      0120=0 A
    3. Count long-running loads at 125%, as NEC 210.20(A) requires, then add the rest. This is the smallest rating allowed

      0+1.25×10=12.5 A
    4. Breakers only come in set sizes, so pick the first one at or above that minimum (NEC 240.6(A))

      smallest standard size ≥ 12.5 A is 15 A
    5. See how much long-running load this breaker may carry: its rating ÷ 1.25

      151.25=12 A
    6. Check how much of the breaker's rating your total load uses

      1015×100=66.67%
  7. 7. Standard breaker size: 20 A

    1. Count long-running loads at 125%, as NEC 210.20(A) requires, then add the rest. This is the smallest rating allowed

      0+1.25×16=20 A
    2. Breakers only come in set sizes, so pick the first one at or above that minimum (NEC 240.6(A))

      smallest standard size ≥ 20 A is 20 A
    3. See how much long-running load this breaker may carry: its rating ÷ 1.25

      201.25=16 A
    4. Check how much of the breaker's rating your total load uses

      1620×100=80%
  8. 8. Standard breaker size: 15 A

    1. Turn the long-running load into amps (current) by dividing watts by volts

      1,500180=8.3333 A
    2. Do the same for the shorter-running load

      0180=0 A
    3. Count long-running loads at 125%, as NEC 210.20(A) requires, then add the rest. This is the smallest rating allowed

      0+1.25×8.3333=10.4167 A
    4. Breakers only come in set sizes, so pick the first one at or above that minimum (NEC 240.6(A))

      smallest standard size ≥ 10.4167 A is 15 A
    5. See how much long-running load this breaker may carry: its rating ÷ 1.25

      151.25=12 A
    6. Check how much of the breaker's rating your total load uses

      8.333315×100=55.56%
  9. 9. Standard breaker size: 15 A

    1. Turn the long-running load into amps (current) by dividing watts by volts

      1,300130=10 A
    2. Do the same for the shorter-running load

      0130=0 A
    3. Count long-running loads at 125%, as NEC 210.20(A) requires, then add the rest. This is the smallest rating allowed

      0+1.25×10=12.5 A
    4. Breakers only come in set sizes, so pick the first one at or above that minimum (NEC 240.6(A))

      smallest standard size ≥ 12.5 A is 15 A
    5. See how much long-running load this breaker may carry: its rating ÷ 1.25

      151.25=12 A
    6. Check how much of the breaker's rating your total load uses

      1015×100=66.67%
  10. 10. Standard breaker size: 20 A

    1. Turn the long-running load into amps (current) by dividing watts by volts

      1,700120=14.1667 A
    2. Do the same for the shorter-running load

      0120=0 A
    3. Count long-running loads at 125%, as NEC 210.20(A) requires, then add the rest. This is the smallest rating allowed

      0+1.25×14.1667=17.7083 A
    4. Breakers only come in set sizes, so pick the first one at or above that minimum (NEC 240.6(A))

      smallest standard size ≥ 17.7083 A is 20 A
    5. See how much long-running load this breaker may carry: its rating ÷ 1.25

      201.25=16 A
    6. Check how much of the breaker's rating your total load uses

      14.166720×100=70.83%