Breaker Size worksheet
Grades 6–7 · CCSS 7.RP.A.3
Calcapedia Solve each problem and show your work. Round answers to 2 decimal places where needed.
- 1.
Problem 1. - Load given in: Watts
- Continuous load (runs 3 hours or more): 1,500 W
- Noncontinuous load: 0 W
- Circuit voltage: 125 V
- Breaker and enclosure are listed for 100% continuous operation: No
Find: Standard breaker size
Answer
- 2.
Problem 2. - Load given in: Watts
- Continuous load (runs 3 hours or more): 1,300 W
- Noncontinuous load: 0 W
- Circuit voltage: 96 V
- Breaker and enclosure are listed for 100% continuous operation: No
Find: Standard breaker size
Answer
- 3.
Problem 3. - Load given in: Amps
- Continuous load (runs 3 hours or more): 15 A
- Noncontinuous load: 0 A
- Breaker and enclosure are listed for 100% continuous operation: No
Find: Standard breaker size
Answer
- 4.
Problem 4. - Load given in: Amps
- Continuous load (runs 3 hours or more): 17 A
- Noncontinuous load: 0 A
- Breaker and enclosure are listed for 100% continuous operation: No
Find: Standard breaker size
Answer
- 5.
Problem 5. - Load given in: Watts
- Continuous load (runs 3 hours or more): 1,500 W
- Noncontinuous load: 0 W
- Circuit voltage: 155 V
- Breaker and enclosure are listed for 100% continuous operation: No
Find: Standard breaker size
Answer
- 6.
Problem 6. - Load given in: Watts
- Continuous load (runs 3 hours or more): 1,200 W
- Noncontinuous load: 0 W
- Circuit voltage: 120 V
- Breaker and enclosure are listed for 100% continuous operation: No
Find: Standard breaker size
Answer
- 7.
Problem 7. - Load given in: Amps
- Continuous load (runs 3 hours or more): 16 A
- Noncontinuous load: 0 A
- Breaker and enclosure are listed for 100% continuous operation: No
Find: Standard breaker size
Answer
- 8.
Problem 8. - Load given in: Watts
- Continuous load (runs 3 hours or more): 1,500 W
- Noncontinuous load: 0 W
- Circuit voltage: 180 V
- Breaker and enclosure are listed for 100% continuous operation: No
Find: Standard breaker size
Answer
- 9.
Problem 9. - Load given in: Watts
- Continuous load (runs 3 hours or more): 1,300 W
- Noncontinuous load: 0 W
- Circuit voltage: 130 V
- Breaker and enclosure are listed for 100% continuous operation: No
Find: Standard breaker size
Answer
- 10.
Problem 10. - Load given in: Watts
- Continuous load (runs 3 hours or more): 1,700 W
- Noncontinuous load: 0 W
- Circuit voltage: 120 V
- Breaker and enclosure are listed for 100% continuous operation: No
Find: Standard breaker size
Answer
Answer key: Breaker Size worksheet
Calcapedia 1. Standard breaker size: 15 A
Turn the long-running load into amps (current) by dividing watts by volts
Do the same for the shorter-running load
Count long-running loads at 125%, as NEC 210.20(A) requires, then add the rest. This is the smallest rating allowed
Breakers only come in set sizes, so pick the first one at or above that minimum (NEC 240.6(A))
See how much long-running load this breaker may carry: its rating ÷ 1.25
Check how much of the breaker's rating your total load uses
2. Standard breaker size: 20 A
Turn the long-running load into amps (current) by dividing watts by volts
Do the same for the shorter-running load
Count long-running loads at 125%, as NEC 210.20(A) requires, then add the rest. This is the smallest rating allowed
Breakers only come in set sizes, so pick the first one at or above that minimum (NEC 240.6(A))
See how much long-running load this breaker may carry: its rating ÷ 1.25
Check how much of the breaker's rating your total load uses
3. Standard breaker size: 20 A
Count long-running loads at 125%, as NEC 210.20(A) requires, then add the rest. This is the smallest rating allowed
Breakers only come in set sizes, so pick the first one at or above that minimum (NEC 240.6(A))
See how much long-running load this breaker may carry: its rating ÷ 1.25
Check how much of the breaker's rating your total load uses
4. Standard breaker size: 25 A
Count long-running loads at 125%, as NEC 210.20(A) requires, then add the rest. This is the smallest rating allowed
Breakers only come in set sizes, so pick the first one at or above that minimum (NEC 240.6(A))
See how much long-running load this breaker may carry: its rating ÷ 1.25
Check how much of the breaker's rating your total load uses
5. Standard breaker size: 15 A
Turn the long-running load into amps (current) by dividing watts by volts
Do the same for the shorter-running load
Count long-running loads at 125%, as NEC 210.20(A) requires, then add the rest. This is the smallest rating allowed
Breakers only come in set sizes, so pick the first one at or above that minimum (NEC 240.6(A))
See how much long-running load this breaker may carry: its rating ÷ 1.25
Check how much of the breaker's rating your total load uses
6. Standard breaker size: 15 A
Turn the long-running load into amps (current) by dividing watts by volts
Do the same for the shorter-running load
Count long-running loads at 125%, as NEC 210.20(A) requires, then add the rest. This is the smallest rating allowed
Breakers only come in set sizes, so pick the first one at or above that minimum (NEC 240.6(A))
See how much long-running load this breaker may carry: its rating ÷ 1.25
Check how much of the breaker's rating your total load uses
7. Standard breaker size: 20 A
Count long-running loads at 125%, as NEC 210.20(A) requires, then add the rest. This is the smallest rating allowed
Breakers only come in set sizes, so pick the first one at or above that minimum (NEC 240.6(A))
See how much long-running load this breaker may carry: its rating ÷ 1.25
Check how much of the breaker's rating your total load uses
8. Standard breaker size: 15 A
Turn the long-running load into amps (current) by dividing watts by volts
Do the same for the shorter-running load
Count long-running loads at 125%, as NEC 210.20(A) requires, then add the rest. This is the smallest rating allowed
Breakers only come in set sizes, so pick the first one at or above that minimum (NEC 240.6(A))
See how much long-running load this breaker may carry: its rating ÷ 1.25
Check how much of the breaker's rating your total load uses
9. Standard breaker size: 15 A
Turn the long-running load into amps (current) by dividing watts by volts
Do the same for the shorter-running load
Count long-running loads at 125%, as NEC 210.20(A) requires, then add the rest. This is the smallest rating allowed
Breakers only come in set sizes, so pick the first one at or above that minimum (NEC 240.6(A))
See how much long-running load this breaker may carry: its rating ÷ 1.25
Check how much of the breaker's rating your total load uses
10. Standard breaker size: 20 A
Turn the long-running load into amps (current) by dividing watts by volts
Do the same for the shorter-running load
Count long-running loads at 125%, as NEC 210.20(A) requires, then add the rest. This is the smallest rating allowed
Breakers only come in set sizes, so pick the first one at or above that minimum (NEC 240.6(A))
See how much long-running load this breaker may carry: its rating ÷ 1.25
Check how much of the breaker's rating your total load uses