Name Date
Conduit Fill worksheet
Grade 7 · CCSS 7.G.B.4, 7.RP.A.3
Calcapedia Solve each problem and show your work. Round answers to 2 decimal places where needed.
- 1.
Problem 1. - Conduit type: PVC Schedule 40
- Trade size: 1/2 in
- Wire size: 2/0 AWG THHN/THWN-2
- Number of these wires: 4
- Wire size, group 2: Other (enter its diameter)
- Number of group 2 wires: 0
- Group 2 wire outside diameter: 0.13 in
- Wire size, group 3: Other (enter its diameter)
- Number of group 3 wires: 1
- Group 3 wire outside diameter: 0.12 in
- This is a nipple 24 in (600 mm) long or shorter: No
Find: Conduit fill
Answer
- 2.
Problem 2. - Conduit type: EMT
- Trade size: 3/4 in
- Wire size: 14 AWG THHN/THWN-2
- Number of these wires: 4
- Wire size, group 2: 1 AWG THHN/THWN-2
- Number of group 2 wires: 0
- Wire size, group 3: 3/0 AWG THHN/THWN-2
- Number of group 3 wires: 0
- This is a nipple 24 in (600 mm) long or shorter: No
Find: Conduit fill
Answer
- 3.
Problem 3. - Conduit type: EMT
- Trade size: 3 in
- Wire size: 1 AWG THHN/THWN-2
- Number of these wires: 4
- Wire size, group 2: 300 kcmil THHN/THWN-2
- Number of group 2 wires: 0
- Wire size, group 3: Other (enter its diameter)
- Number of group 3 wires: 1
- Group 3 wire outside diameter: 0.15 in
- This is a nipple 24 in (600 mm) long or shorter: No
Find: Conduit fill
Answer
- 4.
Problem 4. - Conduit type: EMT
- Trade size: 2 1/2 in
- Wire size: 400 kcmil THHN/THWN-2
- Number of these wires: 4
- Wire size, group 2: 6 AWG THHN/THWN-2
- Number of group 2 wires: 0
- Wire size, group 3: Other (enter its diameter)
- Number of group 3 wires: 0
- Group 3 wire outside diameter: 0.2 in
- This is a nipple 24 in (600 mm) long or shorter: No
Find: Conduit fill
Answer
- 5.
Problem 5. - Conduit type: EMT
- Trade size: 4 in
- Wire size: 8 AWG THHN/THWN-2
- Number of these wires: 4
- Wire size, group 2: 2 AWG THHN/THWN-2
- Number of group 2 wires: 0
- Wire size, group 3: 10 AWG THHN/THWN-2
- Number of group 3 wires: 3
- This is a nipple 24 in (600 mm) long or shorter: No
Find: Conduit fill
Answer
- 6.
Problem 6. - Conduit type: Other (enter its inside diameter)
- Conduit inside diameter: 0.6 in
- Wire size: 4 AWG THHN/THWN-2
- Number of these wires: 3
- Wire size, group 2: 8 AWG THHN/THWN-2
- Number of group 2 wires: 1
- Wire size, group 3: 4 AWG THHN/THWN-2
- Number of group 3 wires: 0
- This is a nipple 24 in (600 mm) long or shorter: No
Find: Conduit fill
Answer
- 7.
Problem 7. - Conduit type: PVC Schedule 40
- Trade size: 3/4 in
- Wire size: 1/0 AWG THHN/THWN-2
- Number of these wires: 5
- Wire size, group 2: 1/0 AWG THHN/THWN-2
- Number of group 2 wires: 0
- Wire size, group 3: 6 AWG THHN/THWN-2
- Number of group 3 wires: 1
- This is a nipple 24 in (600 mm) long or shorter: No
Find: Conduit fill
Answer
- 8.
Problem 8. - Conduit type: EMT
- Trade size: 4 in
- Wire size: 3 AWG THHN/THWN-2
- Number of these wires: 4
- Wire size, group 2: 250 kcmil THHN/THWN-2
- Number of group 2 wires: 0
- Wire size, group 3: 400 kcmil THHN/THWN-2
- Number of group 3 wires: 1
- This is a nipple 24 in (600 mm) long or shorter: No
Find: Conduit fill
Answer
- 9.
Problem 9. - Conduit type: EMT
- Trade size: 1 1/2 in
- Wire size: 2/0 AWG THHN/THWN-2
- Number of these wires: 5
- Wire size, group 2: 4 AWG THHN/THWN-2
- Number of group 2 wires: 0
- Wire size, group 3: 400 kcmil THHN/THWN-2
- Number of group 3 wires: 2
- This is a nipple 24 in (600 mm) long or shorter: No
Find: Conduit fill
Answer
- 10.
Problem 10. - Conduit type: EMT
- Trade size: 1 in
- Wire size: 4 AWG THHN/THWN-2
- Number of these wires: 3
- Wire size, group 2: 500 kcmil THHN/THWN-2
- Number of group 2 wires: 0
- Wire size, group 3: Other (enter its diameter)
- Number of group 3 wires: 0
- Group 3 wire outside diameter: 0.14 in
- This is a nipple 24 in (600 mm) long or shorter: No
Find: Conduit fill
Answer
Answer key: Conduit Fill worksheet
Calcapedia 1. Conduit fill: 333.06%
Find the open space inside the 1/2 in Schedule 40 PVC. Treat it as a circle with inside diameter d = 0.578 in, so its area A = π ÷ 4 × d²
Find the space one 2/0 AWG THHN takes up (0.524 in across, including insulation), then multiply by 4 wires
Find the space one 0.12 in wire takes up (0.12 in across, including insulation), then multiply by 1 wires
Add up the space taken by all the wires
Find the percent fill: the wires' area divided by the conduit's open area, times 100
Look up the fill limit for more than two conductors (40%) in NEC Chapter 9, Table 1, then find how much of the area the wires may use
Work out how many 2/0 AWG THHN wires would fit on their own (each count is checked against its own limit)
2. Conduit fill: 7.52%
Find the open space inside the 3/4 in EMT. Treat it as a circle with inside diameter d = 0.824 in, so its area A = π ÷ 4 × d²
Find the space one 14 AWG THHN takes up (0.113 in across, including insulation), then multiply by 4 wires
Find the percent fill: the wires' area divided by the conduit's open area, times 100
Look up the fill limit for more than two conductors (40%) in NEC Chapter 9, Table 1, then find how much of the area the wires may use
Work out how many 14 AWG THHN wires would fit on their own (each count is checked against its own limit)
3. Conduit fill: 7.11%
Find the open space inside the 3 in EMT. Treat it as a circle with inside diameter d = 3.356 in, so its area A = π ÷ 4 × d²
Find the space one 1 AWG THHN takes up (0.441 in across, including insulation), then multiply by 4 wires
Find the space one 0.15 in wire takes up (0.15 in across, including insulation), then multiply by 1 wires
Add up the space taken by all the wires
Find the percent fill: the wires' area divided by the conduit's open area, times 100
Look up the fill limit for more than two conductors (40%) in NEC Chapter 9, Table 1, then find how much of the area the wires may use
Work out how many 1 AWG THHN wires would fit on their own (each count is checked against its own limit)
4. Conduit fill: 36.68%
Find the open space inside the 2 1/2 in EMT. Treat it as a circle with inside diameter d = 2.731 in, so its area A = π ÷ 4 × d²
Find the space one 400 kcmil THHN takes up (0.827 in across, including insulation), then multiply by 4 wires
Find the percent fill: the wires' area divided by the conduit's open area, times 100
Look up the fill limit for more than two conductors (40%) in NEC Chapter 9, Table 1, then find how much of the area the wires may use
Work out how many 400 kcmil THHN wires would fit on their own (each count is checked against its own limit)
5. Conduit fill: 1.44%
Find the open space inside the 4 in EMT. Treat it as a circle with inside diameter d = 4.334 in, so its area A = π ÷ 4 × d²
Find the space one 8 AWG THHN takes up (0.217 in across, including insulation), then multiply by 4 wires
Find the space one 10 AWG THHN takes up (0.166 in across, including insulation), then multiply by 3 wires
Add up the space taken by all the wires
Find the percent fill: the wires' area divided by the conduit's open area, times 100
Look up the fill limit for more than two conductors (40%) in NEC Chapter 9, Table 1, then find how much of the area the wires may use
Work out how many 8 AWG THHN wires would fit on their own (each count is checked against its own limit)
6. Conduit fill: 100.56%
Find the open space inside the conduit with a 0.6 in bore. Treat it as a circle with inside diameter d = 0.6 in, so its area A = π ÷ 4 × d²
Find the space one 4 AWG THHN takes up (0.324 in across, including insulation), then multiply by 3 wires
Find the space one 8 AWG THHN takes up (0.217 in across, including insulation), then multiply by 1 wires
Add up the space taken by all the wires
Find the percent fill: the wires' area divided by the conduit's open area, times 100
Look up the fill limit for more than two conductors (40%) in NEC Chapter 9, Table 1, then find how much of the area the wires may use
Work out how many 4 AWG THHN wires would fit on their own (each count is checked against its own limit)
7. Conduit fill: 199.87%
Find the open space inside the 3/4 in Schedule 40 PVC. Treat it as a circle with inside diameter d = 0.78 in, so its area A = π ÷ 4 × d²
Find the space one 1/0 AWG THHN takes up (0.48 in across, including insulation), then multiply by 5 wires
Find the space one 6 AWG THHN takes up (0.253 in across, including insulation), then multiply by 1 wires
Add up the space taken by all the wires
Find the percent fill: the wires' area divided by the conduit's open area, times 100
Look up the fill limit for more than two conductors (40%) in NEC Chapter 9, Table 1, then find how much of the area the wires may use
Work out how many 1/0 AWG THHN wires would fit on their own (each count is checked against its own limit)
8. Conduit fill: 6.25%
Find the open space inside the 4 in EMT. Treat it as a circle with inside diameter d = 4.334 in, so its area A = π ÷ 4 × d²
Find the space one 3 AWG THHN takes up (0.35 in across, including insulation), then multiply by 4 wires
Find the space one 400 kcmil THHN takes up (0.827 in across, including insulation), then multiply by 1 wires
Add up the space taken by all the wires
Find the percent fill: the wires' area divided by the conduit's open area, times 100
Look up the fill limit for more than two conductors (40%) in NEC Chapter 9, Table 1, then find how much of the area the wires may use
Work out how many 3 AWG THHN wires would fit on their own (each count is checked against its own limit)
9. Conduit fill: 105.73%
Find the open space inside the 1 1/2 in EMT. Treat it as a circle with inside diameter d = 1.61 in, so its area A = π ÷ 4 × d²
Find the space one 2/0 AWG THHN takes up (0.524 in across, including insulation), then multiply by 5 wires
Find the space one 400 kcmil THHN takes up (0.827 in across, including insulation), then multiply by 2 wires
Add up the space taken by all the wires
Find the percent fill: the wires' area divided by the conduit's open area, times 100
Look up the fill limit for more than two conductors (40%) in NEC Chapter 9, Table 1, then find how much of the area the wires may use
Work out how many 2/0 AWG THHN wires would fit on their own (each count is checked against its own limit)
10. Conduit fill: 28.62%
Find the open space inside the 1 in EMT. Treat it as a circle with inside diameter d = 1.049 in, so its area A = π ÷ 4 × d²
Find the space one 4 AWG THHN takes up (0.324 in across, including insulation), then multiply by 3 wires
Find the percent fill: the wires' area divided by the conduit's open area, times 100
Look up the fill limit for more than two conductors (40%) in NEC Chapter 9, Table 1, then find how much of the area the wires may use
Work out how many 4 AWG THHN wires would fit on their own (each count is checked against its own limit)