Conduit Fill worksheet

Grade 7 · CCSS 7.G.B.4, 7.RP.A.3

Solve each problem and show your work. Round answers to 2 decimal places where needed.

  1. Problem 1.
    • Conduit type: PVC Schedule 40
    • Trade size: 1/2 in
    • Wire size: 2/0 AWG THHN/THWN-2
    • Number of these wires: 4
    • Wire size, group 2: Other (enter its diameter)
    • Number of group 2 wires: 0
    • Group 2 wire outside diameter: 0.13 in
    • Wire size, group 3: Other (enter its diameter)
    • Number of group 3 wires: 1
    • Group 3 wire outside diameter: 0.12 in
    • This is a nipple 24 in (600 mm) long or shorter: No

    Find: Conduit fill

  2. Problem 2.
    • Conduit type: EMT
    • Trade size: 3/4 in
    • Wire size: 14 AWG THHN/THWN-2
    • Number of these wires: 4
    • Wire size, group 2: 1 AWG THHN/THWN-2
    • Number of group 2 wires: 0
    • Wire size, group 3: 3/0 AWG THHN/THWN-2
    • Number of group 3 wires: 0
    • This is a nipple 24 in (600 mm) long or shorter: No

    Find: Conduit fill

  3. Problem 3.
    • Conduit type: EMT
    • Trade size: 3 in
    • Wire size: 1 AWG THHN/THWN-2
    • Number of these wires: 4
    • Wire size, group 2: 300 kcmil THHN/THWN-2
    • Number of group 2 wires: 0
    • Wire size, group 3: Other (enter its diameter)
    • Number of group 3 wires: 1
    • Group 3 wire outside diameter: 0.15 in
    • This is a nipple 24 in (600 mm) long or shorter: No

    Find: Conduit fill

  4. Problem 4.
    • Conduit type: EMT
    • Trade size: 2 1/2 in
    • Wire size: 400 kcmil THHN/THWN-2
    • Number of these wires: 4
    • Wire size, group 2: 6 AWG THHN/THWN-2
    • Number of group 2 wires: 0
    • Wire size, group 3: Other (enter its diameter)
    • Number of group 3 wires: 0
    • Group 3 wire outside diameter: 0.2 in
    • This is a nipple 24 in (600 mm) long or shorter: No

    Find: Conduit fill

  5. Problem 5.
    • Conduit type: EMT
    • Trade size: 4 in
    • Wire size: 8 AWG THHN/THWN-2
    • Number of these wires: 4
    • Wire size, group 2: 2 AWG THHN/THWN-2
    • Number of group 2 wires: 0
    • Wire size, group 3: 10 AWG THHN/THWN-2
    • Number of group 3 wires: 3
    • This is a nipple 24 in (600 mm) long or shorter: No

    Find: Conduit fill

  6. Problem 6.
    • Conduit type: Other (enter its inside diameter)
    • Conduit inside diameter: 0.6 in
    • Wire size: 4 AWG THHN/THWN-2
    • Number of these wires: 3
    • Wire size, group 2: 8 AWG THHN/THWN-2
    • Number of group 2 wires: 1
    • Wire size, group 3: 4 AWG THHN/THWN-2
    • Number of group 3 wires: 0
    • This is a nipple 24 in (600 mm) long or shorter: No

    Find: Conduit fill

  7. Problem 7.
    • Conduit type: PVC Schedule 40
    • Trade size: 3/4 in
    • Wire size: 1/0 AWG THHN/THWN-2
    • Number of these wires: 5
    • Wire size, group 2: 1/0 AWG THHN/THWN-2
    • Number of group 2 wires: 0
    • Wire size, group 3: 6 AWG THHN/THWN-2
    • Number of group 3 wires: 1
    • This is a nipple 24 in (600 mm) long or shorter: No

    Find: Conduit fill

  8. Problem 8.
    • Conduit type: EMT
    • Trade size: 4 in
    • Wire size: 3 AWG THHN/THWN-2
    • Number of these wires: 4
    • Wire size, group 2: 250 kcmil THHN/THWN-2
    • Number of group 2 wires: 0
    • Wire size, group 3: 400 kcmil THHN/THWN-2
    • Number of group 3 wires: 1
    • This is a nipple 24 in (600 mm) long or shorter: No

    Find: Conduit fill

  9. Problem 9.
    • Conduit type: EMT
    • Trade size: 1 1/2 in
    • Wire size: 2/0 AWG THHN/THWN-2
    • Number of these wires: 5
    • Wire size, group 2: 4 AWG THHN/THWN-2
    • Number of group 2 wires: 0
    • Wire size, group 3: 400 kcmil THHN/THWN-2
    • Number of group 3 wires: 2
    • This is a nipple 24 in (600 mm) long or shorter: No

    Find: Conduit fill

  10. Problem 10.
    • Conduit type: EMT
    • Trade size: 1 in
    • Wire size: 4 AWG THHN/THWN-2
    • Number of these wires: 3
    • Wire size, group 2: 500 kcmil THHN/THWN-2
    • Number of group 2 wires: 0
    • Wire size, group 3: Other (enter its diameter)
    • Number of group 3 wires: 0
    • Group 3 wire outside diameter: 0.14 in
    • This is a nipple 24 in (600 mm) long or shorter: No

    Find: Conduit fill

Answer key: Conduit Fill worksheet

  1. 1. Conduit fill: 333.06%

    1. Find the open space inside the 1/2 in Schedule 40 PVC. Treat it as a circle with inside diameter d = 0.578 in, so its area A = π ÷ 4 × d²

      A=π4×0.5782=0.262389 in²
    2. Find the space one 2/0 AWG THHN takes up (0.524 in across, including insulation), then multiply by 4 wires

      4×π4×0.5242=0.862606 in²
    3. Find the space one 0.12 in wire takes up (0.12 in across, including insulation), then multiply by 1 wires

      1×π4×0.122=0.01131 in²
    4. Add up the space taken by all the wires

      0.862606+0.01131=0.873916 in²
    5. Find the percent fill: the wires' area divided by the conduit's open area, times 100

      0.8739160.262389×100=333.0611%
    6. Look up the fill limit for more than two conductors (40%) in NEC Chapter 9, Table 1, then find how much of the area the wires may use

      0.262389×40100=0.104956 in² allowed
    7. Work out how many 2/0 AWG THHN wires would fit on their own (each count is checked against its own limit)

      largest n with n×0.215651 ≤ allowed area: n = 0
  2. 2. Conduit fill: 7.52%

    1. Find the open space inside the 3/4 in EMT. Treat it as a circle with inside diameter d = 0.824 in, so its area A = π ÷ 4 × d²

      A=π4×0.8242=0.533267 in²
    2. Find the space one 14 AWG THHN takes up (0.113 in across, including insulation), then multiply by 4 wires

      4×π4×0.1132=0.040115 in²
    3. Find the percent fill: the wires' area divided by the conduit's open area, times 100

      0.0401150.533267×100=7.5225%
    4. Look up the fill limit for more than two conductors (40%) in NEC Chapter 9, Table 1, then find how much of the area the wires may use

      0.533267×40100=0.213307 in² allowed
    5. Work out how many 14 AWG THHN wires would fit on their own (each count is checked against its own limit)

      largest n with n×0.010029 ≤ allowed area: n = 21
  3. 3. Conduit fill: 7.11%

    1. Find the open space inside the 3 in EMT. Treat it as a circle with inside diameter d = 3.356 in, so its area A = π ÷ 4 × d²

      A=π4×3.3562=8.845732 in²
    2. Find the space one 1 AWG THHN takes up (0.441 in across, including insulation), then multiply by 4 wires

      4×π4×0.4412=0.61098 in²
    3. Find the space one 0.15 in wire takes up (0.15 in across, including insulation), then multiply by 1 wires

      1×π4×0.152=0.017671 in²
    4. Add up the space taken by all the wires

      0.61098+0.017671=0.628652 in²
    5. Find the percent fill: the wires' area divided by the conduit's open area, times 100

      0.6286528.845732×100=7.1068%
    6. Look up the fill limit for more than two conductors (40%) in NEC Chapter 9, Table 1, then find how much of the area the wires may use

      8.845732×40100=3.538293 in² allowed
    7. Work out how many 1 AWG THHN wires would fit on their own (each count is checked against its own limit)

      largest n with n×0.152745 ≤ allowed area: n = 23
  4. 4. Conduit fill: 36.68%

    1. Find the open space inside the 2 1/2 in EMT. Treat it as a circle with inside diameter d = 2.731 in, so its area A = π ÷ 4 × d²

      A=π4×2.7312=5.857783 in²
    2. Find the space one 400 kcmil THHN takes up (0.827 in across, including insulation), then multiply by 4 wires

      4×π4×0.8272=2.148626 in²
    3. Find the percent fill: the wires' area divided by the conduit's open area, times 100

      2.1486265.857783×100=36.6799%
    4. Look up the fill limit for more than two conductors (40%) in NEC Chapter 9, Table 1, then find how much of the area the wires may use

      5.857783×40100=2.343113 in² allowed
    5. Work out how many 400 kcmil THHN wires would fit on their own (each count is checked against its own limit)

      largest n with n×0.537157 ≤ allowed area: n = 4
  5. 5. Conduit fill: 1.44%

    1. Find the open space inside the 4 in EMT. Treat it as a circle with inside diameter d = 4.334 in, so its area A = π ÷ 4 × d²

      A=π4×4.3342=14.75257 in²
    2. Find the space one 8 AWG THHN takes up (0.217 in across, including insulation), then multiply by 4 wires

      4×π4×0.2172=0.147934 in²
    3. Find the space one 10 AWG THHN takes up (0.166 in across, including insulation), then multiply by 3 wires

      3×π4×0.1662=0.064927 in²
    4. Add up the space taken by all the wires

      0.147934+0.064927=0.212862 in²
    5. Find the percent fill: the wires' area divided by the conduit's open area, times 100

      0.21286214.75257×100=1.4429%
    6. Look up the fill limit for more than two conductors (40%) in NEC Chapter 9, Table 1, then find how much of the area the wires may use

      14.75257×40100=5.901028 in² allowed
    7. Work out how many 8 AWG THHN wires would fit on their own (each count is checked against its own limit)

      largest n with n×0.036984 ≤ allowed area: n = 159
  6. 6. Conduit fill: 100.56%

    1. Find the open space inside the conduit with a 0.6 in bore. Treat it as a circle with inside diameter d = 0.6 in, so its area A = π ÷ 4 × d²

      A=π4×0.62=0.282743 in²
    2. Find the space one 4 AWG THHN takes up (0.324 in across, including insulation), then multiply by 3 wires

      3×π4×0.3242=0.247344 in²
    3. Find the space one 8 AWG THHN takes up (0.217 in across, including insulation), then multiply by 1 wires

      1×π4×0.2172=0.036984 in²
    4. Add up the space taken by all the wires

      0.247344+0.036984=0.284327 in²
    5. Find the percent fill: the wires' area divided by the conduit's open area, times 100

      0.2843270.282743×100=100.5603%
    6. Look up the fill limit for more than two conductors (40%) in NEC Chapter 9, Table 1, then find how much of the area the wires may use

      0.282743×40100=0.113097 in² allowed
    7. Work out how many 4 AWG THHN wires would fit on their own (each count is checked against its own limit)

      largest n with n×0.082448 ≤ allowed area: n = 1
  7. 7. Conduit fill: 199.87%

    1. Find the open space inside the 3/4 in Schedule 40 PVC. Treat it as a circle with inside diameter d = 0.78 in, so its area A = π ÷ 4 × d²

      A=π4×0.782=0.477836 in²
    2. Find the space one 1/0 AWG THHN takes up (0.48 in across, including insulation), then multiply by 5 wires

      5×π4×0.482=0.904779 in²
    3. Find the space one 6 AWG THHN takes up (0.253 in across, including insulation), then multiply by 1 wires

      1×π4×0.2532=0.050273 in²
    4. Add up the space taken by all the wires

      0.904779+0.050273=0.955051 in²
    5. Find the percent fill: the wires' area divided by the conduit's open area, times 100

      0.9550510.477836×100=199.87%
    6. Look up the fill limit for more than two conductors (40%) in NEC Chapter 9, Table 1, then find how much of the area the wires may use

      0.477836×40100=0.191134 in² allowed
    7. Work out how many 1/0 AWG THHN wires would fit on their own (each count is checked against its own limit)

      largest n with n×0.180956 ≤ allowed area: n = 1
  8. 8. Conduit fill: 6.25%

    1. Find the open space inside the 4 in EMT. Treat it as a circle with inside diameter d = 4.334 in, so its area A = π ÷ 4 × d²

      A=π4×4.3342=14.75257 in²
    2. Find the space one 3 AWG THHN takes up (0.35 in across, including insulation), then multiply by 4 wires

      4×π4×0.352=0.384845 in²
    3. Find the space one 400 kcmil THHN takes up (0.827 in across, including insulation), then multiply by 1 wires

      1×π4×0.8272=0.537157 in²
    4. Add up the space taken by all the wires

      0.384845+0.537157=0.922002 in²
    5. Find the percent fill: the wires' area divided by the conduit's open area, times 100

      0.92200214.75257×100=6.2498%
    6. Look up the fill limit for more than two conductors (40%) in NEC Chapter 9, Table 1, then find how much of the area the wires may use

      14.75257×40100=5.901028 in² allowed
    7. Work out how many 3 AWG THHN wires would fit on their own (each count is checked against its own limit)

      largest n with n×0.096211 ≤ allowed area: n = 61
  9. 9. Conduit fill: 105.73%

    1. Find the open space inside the 1 1/2 in EMT. Treat it as a circle with inside diameter d = 1.61 in, so its area A = π ÷ 4 × d²

      A=π4×1.612=2.035831 in²
    2. Find the space one 2/0 AWG THHN takes up (0.524 in across, including insulation), then multiply by 5 wires

      5×π4×0.5242=1.078257 in²
    3. Find the space one 400 kcmil THHN takes up (0.827 in across, including insulation), then multiply by 2 wires

      2×π4×0.8272=1.074313 in²
    4. Add up the space taken by all the wires

      1.078257+1.074313=2.152571 in²
    5. Find the percent fill: the wires' area divided by the conduit's open area, times 100

      2.1525712.035831×100=105.7343%
    6. Look up the fill limit for more than two conductors (40%) in NEC Chapter 9, Table 1, then find how much of the area the wires may use

      2.035831×40100=0.814332 in² allowed
    7. Work out how many 2/0 AWG THHN wires would fit on their own (each count is checked against its own limit)

      largest n with n×0.215651 ≤ allowed area: n = 3
  10. 10. Conduit fill: 28.62%

    1. Find the open space inside the 1 in EMT. Treat it as a circle with inside diameter d = 1.049 in, so its area A = π ÷ 4 × d²

      A=π4×1.0492=0.864253 in²
    2. Find the space one 4 AWG THHN takes up (0.324 in across, including insulation), then multiply by 3 wires

      3×π4×0.3242=0.247344 in²
    3. Find the percent fill: the wires' area divided by the conduit's open area, times 100

      0.2473440.864253×100=28.6194%
    4. Look up the fill limit for more than two conductors (40%) in NEC Chapter 9, Table 1, then find how much of the area the wires may use

      0.864253×40100=0.345701 in² allowed
    5. Work out how many 4 AWG THHN wires would fit on their own (each count is checked against its own limit)

      largest n with n×0.082448 ≤ allowed area: n = 4