Heat Loss worksheet

Grades 6–7 · CCSS 6.EE.A.2.c

Solve each problem and show your work. Round answers to 2 decimal places where needed.

  1. Problem 1.
    • Indoor temperature: 60 °F
    • Outdoor design temperature: 11 °F
    • Wall area (excluding windows and doors): 1,400 ft²
    • Wall R-value: 10
    • Window and door area: 150 ft²
    • Window and door U-factor: 0.2
    • Ceiling area (under the attic): 1,600 ft²
    • Ceiling R-value: 46
    • Floor area over unheated space: 0 ft²
    • Floor R-value: 22
    • Heated volume: 10,500 ft³
    • Air changes per hour (leakage): 0.4
    • Heating system efficiency: 78%

    Find: Design heat loss

  2. Problem 2.
    • Indoor temperature: 75 °F
    • Outdoor design temperature: 10 °F
    • Wall area (excluding windows and doors): 1,800 ft²
    • Wall R-value: 15
    • Window and door area: 220 ft²
    • Window and door U-factor: 0.3
    • Ceiling area (under the attic): 1,850 ft²
    • Ceiling R-value: 30
    • Floor area over unheated space: 0 ft²
    • Floor R-value: 21
    • Heated volume: 14,000 ft³
    • Air changes per hour (leakage): 0.5
    • Heating system efficiency: 95%

    Find: Design heat loss

  3. Problem 3.
    • Indoor temperature: 45 °F
    • Outdoor design temperature: 9 °F
    • Wall area (excluding windows and doors): 1,100 ft²
    • Wall R-value: 15
    • Window and door area: 180 ft²
    • Window and door U-factor: 0.3
    • Ceiling area (under the attic): 1,700 ft²
    • Ceiling R-value: 32
    • Floor area over unheated space: 0 ft²
    • Floor R-value: 24
    • Heated volume: 12,000 ft³
    • Air changes per hour (leakage): 0.4
    • Heating system efficiency: 94%

    Find: Design heat loss

  4. Problem 4.
    • Indoor temperature: 64 °F
    • Outdoor design temperature: 9 °F
    • Wall area (excluding windows and doors): 1,250 ft²
    • Wall R-value: 13
    • Window and door area: 140 ft²
    • Window and door U-factor: 0.2
    • Ceiling area (under the attic): 1,400 ft²
    • Ceiling R-value: 38
    • Floor area over unheated space: 0 ft²
    • Floor R-value: 15
    • Heated volume: 11,000 ft³
    • Air changes per hour (leakage): 0.6
    • Heating system efficiency: 78%

    Find: Design heat loss

  5. Problem 5.
    • Indoor temperature: 76 °F
    • Outdoor design temperature: 12 °F
    • Wall area (excluding windows and doors): 1,100 ft²
    • Wall R-value: 14
    • Window and door area: 200 ft²
    • Window and door U-factor: 0.2
    • Ceiling area (under the attic): 1,460 ft²
    • Ceiling R-value: 26
    • Floor area over unheated space: 0 ft²
    • Floor R-value: 24
    • Heated volume: 14,000 ft³
    • Air changes per hour (leakage): 0.5
    • Heating system efficiency: 65%

    Find: Design heat loss

  6. Problem 6.
    • Indoor temperature: 55 °F
    • Outdoor design temperature: 12 °F
    • Wall area (excluding windows and doors): 1,075 ft²
    • Wall R-value: 14
    • Window and door area: 180 ft²
    • Window and door U-factor: 0.4
    • Ceiling area (under the attic): 1,500 ft²
    • Ceiling R-value: 41
    • Floor area over unheated space: 0 ft²
    • Floor R-value: 18
    • Heated volume: 11,000 ft³
    • Air changes per hour (leakage): 0.6
    • Heating system efficiency: 70%

    Find: Design heat loss

  7. Problem 7.
    • Indoor temperature: 80 °F
    • Outdoor design temperature: 10 °F
    • Wall area (excluding windows and doors): 1,550 ft²
    • Wall R-value: 14
    • Window and door area: 240 ft²
    • Window and door U-factor: 0.3
    • Ceiling area (under the attic): 1,520 ft²
    • Ceiling R-value: 42
    • Floor area over unheated space: 0 ft²
    • Floor R-value: 16
    • Heated volume: 12,500 ft³
    • Air changes per hour (leakage): 0.5
    • Heating system efficiency: 85%

    Find: Design heat loss

  8. Problem 8.
    • Indoor temperature: 90 °F
    • Outdoor design temperature: 10 °F
    • Wall area (excluding windows and doors): 1,400 ft²
    • Wall R-value: 10
    • Window and door area: 200 ft²
    • Window and door U-factor: 0.4
    • Ceiling area (under the attic): 1,500 ft²
    • Ceiling R-value: 40
    • Floor area over unheated space: 0 ft²
    • Floor R-value: 17
    • Heated volume: 11,750 ft³
    • Air changes per hour (leakage): 0.4
    • Heating system efficiency: 90%

    Find: Design heat loss

  9. Problem 9.
    • Indoor temperature: 70 °F
    • Outdoor design temperature: 7 °F
    • Wall area (excluding windows and doors): 1,400 ft²
    • Wall R-value: 12
    • Window and door area: 200 ft²
    • Window and door U-factor: 0.3
    • Ceiling area (under the attic): 1,900 ft²
    • Ceiling R-value: 34
    • Floor area over unheated space: 0 ft²
    • Floor R-value: 24
    • Heated volume: 15,250 ft³
    • Air changes per hour (leakage): 0.4
    • Heating system efficiency: 90%

    Find: Design heat loss

  10. Problem 10.
    • Indoor temperature: 75 °F
    • Outdoor design temperature: 11 °F
    • Wall area (excluding windows and doors): 1,200 ft²
    • Wall R-value: 15
    • Window and door area: 160 ft²
    • Window and door U-factor: 0.3
    • Ceiling area (under the attic): 1,600 ft²
    • Ceiling R-value: 36
    • Floor area over unheated space: 0 ft²
    • Floor R-value: 18
    • Heated volume: 14,000 ft³
    • Air changes per hour (leakage): 0.4
    • Heating system efficiency: 68%

    Find: Design heat loss

Answer key: Heat Loss worksheet

  1. 1. Design heat loss: 13,739 BTU/h

    1. Find the temperature gap (ΔT): indoor minus outdoor. A bigger gap pushes heat out faster

      60−11=49 °F
    2. Walls: area times the gap, divided by the R-value (more insulation, less loss)

      1,400×4910=6,860 BTU/h
    3. Windows and doors: the U-factor times the area times the gap

      0.2×150×49=1,470 BTU/h
    4. Ceiling: area times the gap, divided by the R-value

      1,600×4946=1,704.3 BTU/h
    5. Air leaks: 0.018 times the volume, the air changes per hour and the gap (0.018 BTU heats 1 ft³ of air by 1 °F)

      0.018×10,500×0.4×49=3,704.4 BTU/h
    6. Add up every part to get the total heat loss

      6,860+1,470+1,704.3+3,704.4=13,738.7 BTU/h
    7. Divide by the 78% efficiency to get the input rating you need, since output is input times efficiency

      13,738.70.78=17,613.8 BTU/h
  2. 2. Design heat loss: 24,288 BTU/h

    1. Find the temperature gap (ΔT): indoor minus outdoor. A bigger gap pushes heat out faster

      75−10=65 °F
    2. Walls: area times the gap, divided by the R-value (more insulation, less loss)

      1,800×6515=7,800 BTU/h
    3. Windows and doors: the U-factor times the area times the gap

      0.3×220×65=4,290 BTU/h
    4. Ceiling: area times the gap, divided by the R-value

      1,850×6530=4,008.3 BTU/h
    5. Air leaks: 0.018 times the volume, the air changes per hour and the gap (0.018 BTU heats 1 ft³ of air by 1 °F)

      0.018×14,000×0.5×65=8,190 BTU/h
    6. Add up every part to get the total heat loss

      7,800+4,290+4,008.3+8,190=24,288.3 BTU/h
    7. Divide by the 95% efficiency to get the input rating you need, since output is input times efficiency

      24,288.30.95=25,566.7 BTU/h
  3. 3. Design heat loss: 9,607 BTU/h

    1. Find the temperature gap (ΔT): indoor minus outdoor. A bigger gap pushes heat out faster

      45−9=36 °F
    2. Walls: area times the gap, divided by the R-value (more insulation, less loss)

      1,100×3615=2,640 BTU/h
    3. Windows and doors: the U-factor times the area times the gap

      0.3×180×36=1,944 BTU/h
    4. Ceiling: area times the gap, divided by the R-value

      1,700×3632=1,912.5 BTU/h
    5. Air leaks: 0.018 times the volume, the air changes per hour and the gap (0.018 BTU heats 1 ft³ of air by 1 °F)

      0.018×12,000×0.4×36=3,110.4 BTU/h
    6. Add up every part to get the total heat loss

      2,640+1,944+1,912.5+3,110.4=9,606.9 BTU/h
    7. Divide by the 94% efficiency to get the input rating you need, since output is input times efficiency

      9,606.90.94=10,220.1 BTU/h
  4. 4. Design heat loss: 15,389 BTU/h

    1. Find the temperature gap (ΔT): indoor minus outdoor. A bigger gap pushes heat out faster

      64−9=55 °F
    2. Walls: area times the gap, divided by the R-value (more insulation, less loss)

      1,250×5513=5,288.5 BTU/h
    3. Windows and doors: the U-factor times the area times the gap

      0.2×140×55=1,540 BTU/h
    4. Ceiling: area times the gap, divided by the R-value

      1,400×5538=2,026.3 BTU/h
    5. Air leaks: 0.018 times the volume, the air changes per hour and the gap (0.018 BTU heats 1 ft³ of air by 1 °F)

      0.018×11,000×0.6×55=6,534 BTU/h
    6. Add up every part to get the total heat loss

      5,288.5+1,540+2,026.3+6,534=15,388.8 BTU/h
    7. Divide by the 78% efficiency to get the input rating you need, since output is input times efficiency

      15,388.80.78=19,729.2 BTU/h
  5. 5. Design heat loss: 19,246 BTU/h

    1. Find the temperature gap (ΔT): indoor minus outdoor. A bigger gap pushes heat out faster

      76−12=64 °F
    2. Walls: area times the gap, divided by the R-value (more insulation, less loss)

      1,100×6414=5,028.6 BTU/h
    3. Windows and doors: the U-factor times the area times the gap

      0.2×200×64=2,560 BTU/h
    4. Ceiling: area times the gap, divided by the R-value

      1,460×6426=3,593.8 BTU/h
    5. Air leaks: 0.018 times the volume, the air changes per hour and the gap (0.018 BTU heats 1 ft³ of air by 1 °F)

      0.018×14,000×0.5×64=8,064 BTU/h
    6. Add up every part to get the total heat loss

      5,028.6+2,560+3,593.8+8,064=19,246.4 BTU/h
    7. Divide by the 65% efficiency to get the input rating you need, since output is input times efficiency

      19,246.40.65=29,609.9 BTU/h
  6. 6. Design heat loss: 13,079 BTU/h

    1. Find the temperature gap (ΔT): indoor minus outdoor. A bigger gap pushes heat out faster

      55−12=43 °F
    2. Walls: area times the gap, divided by the R-value (more insulation, less loss)

      1,075×4314=3,301.8 BTU/h
    3. Windows and doors: the U-factor times the area times the gap

      0.4×180×43=3,096 BTU/h
    4. Ceiling: area times the gap, divided by the R-value

      1,500×4341=1,573.2 BTU/h
    5. Air leaks: 0.018 times the volume, the air changes per hour and the gap (0.018 BTU heats 1 ft³ of air by 1 °F)

      0.018×11,000×0.6×43=5,108.4 BTU/h
    6. Add up every part to get the total heat loss

      3,301.8+3,096+1,573.2+5,108.4=13,079.4 BTU/h
    7. Divide by the 70% efficiency to get the input rating you need, since output is input times efficiency

      13,079.40.7=18,684.8 BTU/h
  7. 7. Design heat loss: 23,198 BTU/h

    1. Find the temperature gap (ΔT): indoor minus outdoor. A bigger gap pushes heat out faster

      80−10=70 °F
    2. Walls: area times the gap, divided by the R-value (more insulation, less loss)

      1,550×7014=7,750 BTU/h
    3. Windows and doors: the U-factor times the area times the gap

      0.3×240×70=5,040 BTU/h
    4. Ceiling: area times the gap, divided by the R-value

      1,520×7042=2,533.3 BTU/h
    5. Air leaks: 0.018 times the volume, the air changes per hour and the gap (0.018 BTU heats 1 ft³ of air by 1 °F)

      0.018×12,500×0.5×70=7,875 BTU/h
    6. Add up every part to get the total heat loss

      7,750+5,040+2,533.3+7,875=23,198.3 BTU/h
    7. Divide by the 85% efficiency to get the input rating you need, since output is input times efficiency

      23,198.30.85=27,292.2 BTU/h
  8. 8. Design heat loss: 27,368 BTU/h

    1. Find the temperature gap (ΔT): indoor minus outdoor. A bigger gap pushes heat out faster

      90−10=80 °F
    2. Walls: area times the gap, divided by the R-value (more insulation, less loss)

      1,400×8010=11,200 BTU/h
    3. Windows and doors: the U-factor times the area times the gap

      0.4×200×80=6,400 BTU/h
    4. Ceiling: area times the gap, divided by the R-value

      1,500×8040=3,000 BTU/h
    5. Air leaks: 0.018 times the volume, the air changes per hour and the gap (0.018 BTU heats 1 ft³ of air by 1 °F)

      0.018×11,750×0.4×80=6,768 BTU/h
    6. Add up every part to get the total heat loss

      11,200+6,400+3,000+6,768=27,368 BTU/h
    7. Divide by the 90% efficiency to get the input rating you need, since output is input times efficiency

      27,3680.9=30,408.9 BTU/h
  9. 9. Design heat loss: 21,568 BTU/h

    1. Find the temperature gap (ΔT): indoor minus outdoor. A bigger gap pushes heat out faster

      70−7=63 °F
    2. Walls: area times the gap, divided by the R-value (more insulation, less loss)

      1,400×6312=7,350 BTU/h
    3. Windows and doors: the U-factor times the area times the gap

      0.3×200×63=3,780 BTU/h
    4. Ceiling: area times the gap, divided by the R-value

      1,900×6334=3,520.6 BTU/h
    5. Air leaks: 0.018 times the volume, the air changes per hour and the gap (0.018 BTU heats 1 ft³ of air by 1 °F)

      0.018×15,250×0.4×63=6,917.4 BTU/h
    6. Add up every part to get the total heat loss

      7,350+3,780+3,520.6+6,917.4=21,568 BTU/h
    7. Divide by the 90% efficiency to get the input rating you need, since output is input times efficiency

      21,5680.9=23,964.4 BTU/h
  10. 10. Design heat loss: 17,488 BTU/h

    1. Find the temperature gap (ΔT): indoor minus outdoor. A bigger gap pushes heat out faster

      75−11=64 °F
    2. Walls: area times the gap, divided by the R-value (more insulation, less loss)

      1,200×6415=5,120 BTU/h
    3. Windows and doors: the U-factor times the area times the gap

      0.3×160×64=3,072 BTU/h
    4. Ceiling: area times the gap, divided by the R-value

      1,600×6436=2,844.4 BTU/h
    5. Air leaks: 0.018 times the volume, the air changes per hour and the gap (0.018 BTU heats 1 ft³ of air by 1 °F)

      0.018×14,000×0.4×64=6,451.2 BTU/h
    6. Add up every part to get the total heat loss

      5,120+3,072+2,844.4+6,451.2=17,487.6 BTU/h
    7. Divide by the 68% efficiency to get the input rating you need, since output is input times efficiency

      17,487.60.68=25,717.1 BTU/h