Name Date
Heat Loss worksheet
Grades 6–7 · CCSS 6.EE.A.2.c
Calcapedia Solve each problem and show your work. Round answers to 2 decimal places where needed.
- 1.
Problem 1. - Indoor temperature: 60 °F
- Outdoor design temperature: 11 °F
- Wall area (excluding windows and doors): 1,400 ft²
- Wall R-value: 10
- Window and door area: 150 ft²
- Window and door U-factor: 0.2
- Ceiling area (under the attic): 1,600 ft²
- Ceiling R-value: 46
- Floor area over unheated space: 0 ft²
- Floor R-value: 22
- Heated volume: 10,500 ft³
- Air changes per hour (leakage): 0.4
- Heating system efficiency: 78%
Find: Design heat loss
Answer
- 2.
Problem 2. - Indoor temperature: 75 °F
- Outdoor design temperature: 10 °F
- Wall area (excluding windows and doors): 1,800 ft²
- Wall R-value: 15
- Window and door area: 220 ft²
- Window and door U-factor: 0.3
- Ceiling area (under the attic): 1,850 ft²
- Ceiling R-value: 30
- Floor area over unheated space: 0 ft²
- Floor R-value: 21
- Heated volume: 14,000 ft³
- Air changes per hour (leakage): 0.5
- Heating system efficiency: 95%
Find: Design heat loss
Answer
- 3.
Problem 3. - Indoor temperature: 45 °F
- Outdoor design temperature: 9 °F
- Wall area (excluding windows and doors): 1,100 ft²
- Wall R-value: 15
- Window and door area: 180 ft²
- Window and door U-factor: 0.3
- Ceiling area (under the attic): 1,700 ft²
- Ceiling R-value: 32
- Floor area over unheated space: 0 ft²
- Floor R-value: 24
- Heated volume: 12,000 ft³
- Air changes per hour (leakage): 0.4
- Heating system efficiency: 94%
Find: Design heat loss
Answer
- 4.
Problem 4. - Indoor temperature: 64 °F
- Outdoor design temperature: 9 °F
- Wall area (excluding windows and doors): 1,250 ft²
- Wall R-value: 13
- Window and door area: 140 ft²
- Window and door U-factor: 0.2
- Ceiling area (under the attic): 1,400 ft²
- Ceiling R-value: 38
- Floor area over unheated space: 0 ft²
- Floor R-value: 15
- Heated volume: 11,000 ft³
- Air changes per hour (leakage): 0.6
- Heating system efficiency: 78%
Find: Design heat loss
Answer
- 5.
Problem 5. - Indoor temperature: 76 °F
- Outdoor design temperature: 12 °F
- Wall area (excluding windows and doors): 1,100 ft²
- Wall R-value: 14
- Window and door area: 200 ft²
- Window and door U-factor: 0.2
- Ceiling area (under the attic): 1,460 ft²
- Ceiling R-value: 26
- Floor area over unheated space: 0 ft²
- Floor R-value: 24
- Heated volume: 14,000 ft³
- Air changes per hour (leakage): 0.5
- Heating system efficiency: 65%
Find: Design heat loss
Answer
- 6.
Problem 6. - Indoor temperature: 55 °F
- Outdoor design temperature: 12 °F
- Wall area (excluding windows and doors): 1,075 ft²
- Wall R-value: 14
- Window and door area: 180 ft²
- Window and door U-factor: 0.4
- Ceiling area (under the attic): 1,500 ft²
- Ceiling R-value: 41
- Floor area over unheated space: 0 ft²
- Floor R-value: 18
- Heated volume: 11,000 ft³
- Air changes per hour (leakage): 0.6
- Heating system efficiency: 70%
Find: Design heat loss
Answer
- 7.
Problem 7. - Indoor temperature: 80 °F
- Outdoor design temperature: 10 °F
- Wall area (excluding windows and doors): 1,550 ft²
- Wall R-value: 14
- Window and door area: 240 ft²
- Window and door U-factor: 0.3
- Ceiling area (under the attic): 1,520 ft²
- Ceiling R-value: 42
- Floor area over unheated space: 0 ft²
- Floor R-value: 16
- Heated volume: 12,500 ft³
- Air changes per hour (leakage): 0.5
- Heating system efficiency: 85%
Find: Design heat loss
Answer
- 8.
Problem 8. - Indoor temperature: 90 °F
- Outdoor design temperature: 10 °F
- Wall area (excluding windows and doors): 1,400 ft²
- Wall R-value: 10
- Window and door area: 200 ft²
- Window and door U-factor: 0.4
- Ceiling area (under the attic): 1,500 ft²
- Ceiling R-value: 40
- Floor area over unheated space: 0 ft²
- Floor R-value: 17
- Heated volume: 11,750 ft³
- Air changes per hour (leakage): 0.4
- Heating system efficiency: 90%
Find: Design heat loss
Answer
- 9.
Problem 9. - Indoor temperature: 70 °F
- Outdoor design temperature: 7 °F
- Wall area (excluding windows and doors): 1,400 ft²
- Wall R-value: 12
- Window and door area: 200 ft²
- Window and door U-factor: 0.3
- Ceiling area (under the attic): 1,900 ft²
- Ceiling R-value: 34
- Floor area over unheated space: 0 ft²
- Floor R-value: 24
- Heated volume: 15,250 ft³
- Air changes per hour (leakage): 0.4
- Heating system efficiency: 90%
Find: Design heat loss
Answer
- 10.
Problem 10. - Indoor temperature: 75 °F
- Outdoor design temperature: 11 °F
- Wall area (excluding windows and doors): 1,200 ft²
- Wall R-value: 15
- Window and door area: 160 ft²
- Window and door U-factor: 0.3
- Ceiling area (under the attic): 1,600 ft²
- Ceiling R-value: 36
- Floor area over unheated space: 0 ft²
- Floor R-value: 18
- Heated volume: 14,000 ft³
- Air changes per hour (leakage): 0.4
- Heating system efficiency: 68%
Find: Design heat loss
Answer
Answer key: Heat Loss worksheet
Calcapedia 1. Design heat loss: 13,739 BTU/h
Find the temperature gap (ΔT): indoor minus outdoor. A bigger gap pushes heat out faster
Walls: area times the gap, divided by the R-value (more insulation, less loss)
Windows and doors: the U-factor times the area times the gap
Ceiling: area times the gap, divided by the R-value
Air leaks: 0.018 times the volume, the air changes per hour and the gap (0.018 BTU heats 1 ft³ of air by 1 °F)
Add up every part to get the total heat loss
Divide by the 78% efficiency to get the input rating you need, since output is input times efficiency
2. Design heat loss: 24,288 BTU/h
Find the temperature gap (ΔT): indoor minus outdoor. A bigger gap pushes heat out faster
Walls: area times the gap, divided by the R-value (more insulation, less loss)
Windows and doors: the U-factor times the area times the gap
Ceiling: area times the gap, divided by the R-value
Air leaks: 0.018 times the volume, the air changes per hour and the gap (0.018 BTU heats 1 ft³ of air by 1 °F)
Add up every part to get the total heat loss
Divide by the 95% efficiency to get the input rating you need, since output is input times efficiency
3. Design heat loss: 9,607 BTU/h
Find the temperature gap (ΔT): indoor minus outdoor. A bigger gap pushes heat out faster
Walls: area times the gap, divided by the R-value (more insulation, less loss)
Windows and doors: the U-factor times the area times the gap
Ceiling: area times the gap, divided by the R-value
Air leaks: 0.018 times the volume, the air changes per hour and the gap (0.018 BTU heats 1 ft³ of air by 1 °F)
Add up every part to get the total heat loss
Divide by the 94% efficiency to get the input rating you need, since output is input times efficiency
4. Design heat loss: 15,389 BTU/h
Find the temperature gap (ΔT): indoor minus outdoor. A bigger gap pushes heat out faster
Walls: area times the gap, divided by the R-value (more insulation, less loss)
Windows and doors: the U-factor times the area times the gap
Ceiling: area times the gap, divided by the R-value
Air leaks: 0.018 times the volume, the air changes per hour and the gap (0.018 BTU heats 1 ft³ of air by 1 °F)
Add up every part to get the total heat loss
Divide by the 78% efficiency to get the input rating you need, since output is input times efficiency
5. Design heat loss: 19,246 BTU/h
Find the temperature gap (ΔT): indoor minus outdoor. A bigger gap pushes heat out faster
Walls: area times the gap, divided by the R-value (more insulation, less loss)
Windows and doors: the U-factor times the area times the gap
Ceiling: area times the gap, divided by the R-value
Air leaks: 0.018 times the volume, the air changes per hour and the gap (0.018 BTU heats 1 ft³ of air by 1 °F)
Add up every part to get the total heat loss
Divide by the 65% efficiency to get the input rating you need, since output is input times efficiency
6. Design heat loss: 13,079 BTU/h
Find the temperature gap (ΔT): indoor minus outdoor. A bigger gap pushes heat out faster
Walls: area times the gap, divided by the R-value (more insulation, less loss)
Windows and doors: the U-factor times the area times the gap
Ceiling: area times the gap, divided by the R-value
Air leaks: 0.018 times the volume, the air changes per hour and the gap (0.018 BTU heats 1 ft³ of air by 1 °F)
Add up every part to get the total heat loss
Divide by the 70% efficiency to get the input rating you need, since output is input times efficiency
7. Design heat loss: 23,198 BTU/h
Find the temperature gap (ΔT): indoor minus outdoor. A bigger gap pushes heat out faster
Walls: area times the gap, divided by the R-value (more insulation, less loss)
Windows and doors: the U-factor times the area times the gap
Ceiling: area times the gap, divided by the R-value
Air leaks: 0.018 times the volume, the air changes per hour and the gap (0.018 BTU heats 1 ft³ of air by 1 °F)
Add up every part to get the total heat loss
Divide by the 85% efficiency to get the input rating you need, since output is input times efficiency
8. Design heat loss: 27,368 BTU/h
Find the temperature gap (ΔT): indoor minus outdoor. A bigger gap pushes heat out faster
Walls: area times the gap, divided by the R-value (more insulation, less loss)
Windows and doors: the U-factor times the area times the gap
Ceiling: area times the gap, divided by the R-value
Air leaks: 0.018 times the volume, the air changes per hour and the gap (0.018 BTU heats 1 ft³ of air by 1 °F)
Add up every part to get the total heat loss
Divide by the 90% efficiency to get the input rating you need, since output is input times efficiency
9. Design heat loss: 21,568 BTU/h
Find the temperature gap (ΔT): indoor minus outdoor. A bigger gap pushes heat out faster
Walls: area times the gap, divided by the R-value (more insulation, less loss)
Windows and doors: the U-factor times the area times the gap
Ceiling: area times the gap, divided by the R-value
Air leaks: 0.018 times the volume, the air changes per hour and the gap (0.018 BTU heats 1 ft³ of air by 1 °F)
Add up every part to get the total heat loss
Divide by the 90% efficiency to get the input rating you need, since output is input times efficiency
10. Design heat loss: 17,488 BTU/h
Find the temperature gap (ΔT): indoor minus outdoor. A bigger gap pushes heat out faster
Walls: area times the gap, divided by the R-value (more insulation, less loss)
Windows and doors: the U-factor times the area times the gap
Ceiling: area times the gap, divided by the R-value
Air leaks: 0.018 times the volume, the air changes per hour and the gap (0.018 BTU heats 1 ft³ of air by 1 °F)
Add up every part to get the total heat loss
Divide by the 68% efficiency to get the input rating you need, since output is input times efficiency