Heating BTU worksheet

Grades 6–7 · CCSS 6.EE.A.2.c

Solve each problem and show your work. Round answers to 2 decimal places where needed.

  1. Problem 1.
    • Units: Meters and °C
    • Floor area to heat: 150 m²
    • Ceiling height: 2 m
    • Insulation and air sealing: Poor: older home, little insulation, single-pane windows, drafty
    • Walls that face outdoors: About half (a corner room)
    • What's under the floor: A heated basement or another heated floor
    • Heating ducts: No ducts (space heater, baseboard or ductless)
    • Indoor temperature you want: 17 °C
    • Outdoor design temperature: -12 °C
    • Heater type: Gas, propane or oil furnace
    • Furnace efficiency (AFUE): 80%

    Find: Heat needed (heater output)

  2. Problem 2.
    • Units: Feet and °F
    • Floor area to heat: 1,800 ft²
    • Ceiling height: 7 ft
    • Insulation and air sealing: Poor: older home, little insulation, single-pane windows, drafty
    • Walls that face outdoors: About half (a corner room)
    • What's under the floor: An unheated crawlspace or basement
    • Heating ducts: No ducts (space heater, baseboard or ductless)
    • Indoor temperature you want: 55 °F
    • Outdoor design temperature: 8 °F
    • Heater type: Gas, propane or oil furnace
    • Furnace efficiency (AFUE): 100%

    Find: Heat needed (heater output)

  3. Problem 3.
    • Units: Meters and °C
    • Floor area to heat: 200 m²
    • Ceiling height: 2 m
    • Insulation and air sealing: Average: insulated walls and attic, double-pane windows
    • Walls that face outdoors: All of them (a whole house or a detached space)
    • What's under the floor: A heated basement or another heated floor
    • Heating ducts: No ducts (space heater, baseboard or ductless)
    • Indoor temperature you want: 28 °C
    • Outdoor design temperature: -13 °C
    • Heater type: Electric heater (100% efficient)

    Find: Heat needed (heater output)

  4. Problem 4.
    • Units: Meters and °C
    • Floor area to heat: 152 m²
    • Ceiling height: 2.8 m
    • Insulation and air sealing: Poor: older home, little insulation, single-pane windows, drafty
    • Walls that face outdoors: About half (a corner room)
    • What's under the floor: A concrete slab on the ground
    • Heating ducts: Ducts inside the heated space
    • Indoor temperature you want: 21 °C
    • Outdoor design temperature: -12 °C
    • Heater type: Gas, propane or oil furnace
    • Furnace efficiency (AFUE): 65%

    Find: Heat needed (heater output)

  5. Problem 5.
    • Units: Meters and °C
    • Floor area to heat: 180 m²
    • Ceiling height: 2.8 m
    • Insulation and air sealing: Poor: older home, little insulation, single-pane windows, drafty
    • Walls that face outdoors: About half (a corner room)
    • What's under the floor: An unheated crawlspace or basement
    • Heating ducts: Ducts in an unheated attic, crawlspace or garage (+20%)
    • Indoor temperature you want: 24 °C
    • Outdoor design temperature: -8 °C
    • Heater type: Electric heater (100% efficient)

    Find: Heat needed (heater output)

  6. Problem 6.
    • Units: Meters and °C
    • Floor area to heat: 140 m²
    • Ceiling height: 1.8 m
    • Insulation and air sealing: Poor: older home, little insulation, single-pane windows, drafty
    • Walls that face outdoors: About a quarter (a room with one outside wall)
    • What's under the floor: A concrete slab on the ground
    • Heating ducts: No ducts (space heater, baseboard or ductless)
    • Indoor temperature you want: 21 °C
    • Outdoor design temperature: -11 °C
    • Heater type: Electric heater (100% efficient)

    Find: Heat needed (heater output)

  7. Problem 7.
    • Units: Feet and °F
    • Floor area to heat: 1,400 ft²
    • Ceiling height: 8 ft
    • Insulation and air sealing: Good: newer, well insulated and sealed, low-e windows
    • Walls that face outdoors: All of them (a whole house or a detached space)
    • What's under the floor: A heated basement or another heated floor
    • Heating ducts: Ducts inside the heated space
    • Indoor temperature you want: 66 °F
    • Outdoor design temperature: 12 °F
    • Heater type: Gas, propane or oil furnace
    • Furnace efficiency (AFUE): 80%

    Find: Heat needed (heater output)

  8. Problem 8.
    • Units: Meters and °C
    • Floor area to heat: 120 m²
    • Ceiling height: 2.7 m
    • Insulation and air sealing: Average: insulated walls and attic, double-pane windows
    • Walls that face outdoors: About half (a corner room)
    • What's under the floor: A concrete slab on the ground
    • Heating ducts: Ducts in an unheated attic, crawlspace or garage (+20%)
    • Indoor temperature you want: 17 °C
    • Outdoor design temperature: -13 °C
    • Heater type: Electric heater (100% efficient)

    Find: Heat needed (heater output)

  9. Problem 9.
    • Units: Feet and °F
    • Floor area to heat: 1,500 ft²
    • Ceiling height: 7 ft
    • Insulation and air sealing: Good: newer, well insulated and sealed, low-e windows
    • Walls that face outdoors: About a quarter (a room with one outside wall)
    • What's under the floor: A concrete slab on the ground
    • Heating ducts: No ducts (space heater, baseboard or ductless)
    • Indoor temperature you want: 64 °F
    • Outdoor design temperature: 8 °F
    • Heater type: Gas, propane or oil furnace
    • Furnace efficiency (AFUE): 70%

    Find: Heat needed (heater output)

  10. Problem 10.
    • Units: Feet and °F
    • Floor area to heat: 1,800 ft²
    • Ceiling height: 8 ft
    • Insulation and air sealing: Good: newer, well insulated and sealed, low-e windows
    • Walls that face outdoors: About half (a corner room)
    • What's under the floor: A heated basement or another heated floor
    • Heating ducts: Ducts inside the heated space
    • Indoor temperature you want: 50 °F
    • Outdoor design temperature: 8 °F
    • Heater type: Electric heater (100% efficient)

    Find: Heat needed (heater output)

Answer key: Heating BTU worksheet

  1. 1. Heat needed (heater output): 32,572 BTU/h

    1. Change to feet and °F, the units the insulation values use (1 ft² = 0.09290304 m², 1 ft = 0.3048 m, 1 °C of difference = 1.8 °F)

      150 m²0.09290304=1,614.59 ft²
    2. Find how much warmer you want it inside than outside. This temperature rise drives every heat loss below

      17−(−12)×1.8=52.2 °F
    3. Picture the space as a square box. Its outside wall area is the distance around (4 × √area) times the height, times the 50% that faces outdoors

      4×1,614.59×6.5617×0.5=527.32 ft²
    4. Heat through the solid walls (85% of the wall area at R-4): area × temperature rise ÷ R-value

      448.22×52.24=5,849.32 BTU/h
    5. Heat through windows and doors (15% of the wall area at U-1): area × U-factor × temperature rise

      79.1×1×52.2=4,128.93 BTU/h
    6. Heat through the ceiling into the attic (R-11)

      1,614.59×52.211=7,661.95 BTU/h
    7. Heat carried off by air leaking in and out: 0.018 × volume × 1.5 air changes an hour × temperature rise

      0.018×10,594.4×1.5×52.2=14,931.75 BTU/h
    8. Add the four parts. A heated space below loses no heat through the floor

      5,849.32+4,128.93+7,661.95+14,931.75=32,571.94 BTU/h
    9. With no ducts, the heat goes straight into the room

      heat needed=32,571.94 BTU/h
    10. Change to kilowatts (1 kW = 3,412.14 BTU/h)

      32,571.943,412.14=9.546 kW
    11. A furnace that is 80% efficient must burn more fuel than the heat it delivers, so divide by its efficiency

      32,571.940.8=40,714.93 BTU/h
    12. Round the input up to the next 10,000 BTU/h to pick a size

      size=50,000 BTU/h furnace (input)
  2. 2. Heat needed (heater output): 54,950 BTU/h

    1. Find how much warmer you want it inside than outside. This temperature rise drives every heat loss below

      55−8=47 °F
    2. Picture the space as a square box. Its outside wall area is the distance around (4 × √area) times the height, times the 50% that faces outdoors

      4×1,800×7×0.5=593.97 ft²
    3. Heat through the solid walls (85% of the wall area at R-4): area × temperature rise ÷ R-value

      504.87×474=5,932.27 BTU/h
    4. Heat through windows and doors (15% of the wall area at U-1): area × U-factor × temperature rise

      89.1×1×47=4,187.49 BTU/h
    5. Heat through the ceiling into the attic (R-11)

      1,800×4711=7,690.91 BTU/h
    6. Heat carried off by air leaking in and out: 0.018 × volume × 1.5 air changes an hour × temperature rise

      0.018×12,600×1.5×47=15,989.4 BTU/h
    7. Heat lost down through the floor (R-4). The full temperature rise is used, because a vented crawlspace can get nearly as cold as outdoors

      1,800×474=21,150 BTU/h
    8. Add the parts to get the heat the house loses on a design-cold day

      5,932.27+4,187.49+7,690.91+15,989.4+21,150=54,950.07 BTU/h
    9. With no ducts, the heat goes straight into the room

      heat needed=54,950.07 BTU/h
    10. Change to kilowatts (1 kW = 3,412.14 BTU/h)

      54,950.073,412.14=16.104 kW
    11. A furnace that is 100% efficient must burn more fuel than the heat it delivers, so divide by its efficiency

      54,950.071=54,950.07 BTU/h
    12. Round the input up to the next 10,000 BTU/h to pick a size

      size=60,000 BTU/h furnace (input)
  3. 3. Heat needed (heater output): 31,986 BTU/h

    1. Change to feet and °F, the units the insulation values use (1 ft² = 0.09290304 m², 1 ft = 0.3048 m, 1 °C of difference = 1.8 °F)

      200 m²0.09290304=2,152.78 ft²
    2. Find how much warmer you want it inside than outside. This temperature rise drives every heat loss below

      28−(−13)×1.8=73.8 °F
    3. Picture the space as a square box. Its outside wall area is the distance around (4 × √area) times the height

      4×2,152.78×6.5617=1,217.8 ft²
    4. Heat through the solid walls (85% of the wall area at R-13): area × temperature rise ÷ R-value

      1,035.13×73.813=5,876.34 BTU/h
    5. Heat through windows and doors (15% of the wall area at U-0.5): area × U-factor × temperature rise

      182.67×0.5×73.8=6,740.51 BTU/h
    6. Heat through the ceiling into the attic (R-30)

      2,152.78×73.830=5,295.84 BTU/h
    7. Heat carried off by air leaking in and out: 0.018 × volume × 0.75 air changes an hour × temperature rise

      0.018×14,125.87×0.75×73.8=14,073.6 BTU/h
    8. Add the four parts. A heated space below loses no heat through the floor

      5,876.34+6,740.51+5,295.84+14,073.6=31,986.29 BTU/h
    9. With no ducts, the heat goes straight into the room

      heat needed=31,986.29 BTU/h
    10. Change to kilowatts (1 kW = 3,412.14 BTU/h)

      31,986.293,412.14=9.374 kW
    11. Electric heat turns all its power into heat. Round the watts up to the next 500 W to pick a size

      9,374 W → size=9,500 W electric heat
  4. 4. Heat needed (heater output): 52,450 BTU/h

    1. Change to feet and °F, the units the insulation values use (1 ft² = 0.09290304 m², 1 ft = 0.3048 m, 1 °C of difference = 1.8 °F)

      152 m²0.09290304=1,636.11 ft²
    2. Find how much warmer you want it inside than outside. This temperature rise drives every heat loss below

      21−(−12)×1.8=59.4 °F
    3. Picture the space as a square box. Its outside wall area is the distance around (4 × √area) times the height, times the 50% that faces outdoors

      4×1,636.11×9.1864×0.5=743.16 ft²
    4. Heat through the solid walls (85% of the wall area at R-4): area × temperature rise ÷ R-value

      631.68×59.44=9,380.48 BTU/h
    5. Heat through windows and doors (15% of the wall area at U-1): area × U-factor × temperature rise

      111.47×1×59.4=6,621.52 BTU/h
    6. Heat through the ceiling into the attic (R-11)

      1,636.11×59.411=8,835.02 BTU/h
    7. Heat carried off by air leaking in and out: 0.018 × volume × 1.5 air changes an hour × temperature rise

      0.018×15,029.92×1.5×59.4=24,104.99 BTU/h
    8. Heat lost through the edge of the slab: 0.73 BTU/h for each foot of outside edge and each degree (no edge insulation)

      0.73×80.9×59.4=3,507.89 BTU/h
    9. Add the parts to get the heat the house loses on a design-cold day

      9,380.48+6,621.52+8,835.02+24,104.99+3,507.89=52,449.9 BTU/h
    10. The ducts are inside the heated space, so any heat they lose stays in the house

      heat needed=52,449.9 BTU/h
    11. Change to kilowatts (1 kW = 3,412.14 BTU/h)

      52,449.93,412.14=15.372 kW
    12. A furnace that is 65% efficient must burn more fuel than the heat it delivers, so divide by its efficiency

      52,449.90.65=80,692.16 BTU/h
    13. Round the input up to the next 10,000 BTU/h to pick a size

      size=90,000 BTU/h furnace (input)
  5. 5. Heat needed (heater output): 99,134 BTU/h

    1. Change to feet and °F, the units the insulation values use (1 ft² = 0.09290304 m², 1 ft = 0.3048 m, 1 °C of difference = 1.8 °F)

      180 m²0.09290304=1,937.5 ft²
    2. Find how much warmer you want it inside than outside. This temperature rise drives every heat loss below

      24−(−8)×1.8=57.6 °F
    3. Picture the space as a square box. Its outside wall area is the distance around (4 × √area) times the height, times the 50% that faces outdoors

      4×1,937.5×9.1864×0.5=808.71 ft²
    4. Heat through the solid walls (85% of the wall area at R-4): area × temperature rise ÷ R-value

      687.41×57.64=9,898.65 BTU/h
    5. Heat through windows and doors (15% of the wall area at U-1): area × U-factor × temperature rise

      121.31×1×57.6=6,987.28 BTU/h
    6. Heat through the ceiling into the attic (R-11)

      1,937.5×57.611=10,145.47 BTU/h
    7. Heat carried off by air leaking in and out: 0.018 × volume × 1.5 air changes an hour × temperature rise

      0.018×17,798.59×1.5×57.6=27,680.37 BTU/h
    8. Heat lost down through the floor (R-4). The full temperature rise is used, because a vented crawlspace can get nearly as cold as outdoors

      1,937.5×57.64=27,900.06 BTU/h
    9. Add the parts to get the heat the house loses on a design-cold day

      9,898.65+6,987.28+10,145.47+27,680.37+27,900.06=82,611.83 BTU/h
    10. Ducts in an unheated attic, crawlspace or garage leak and lose heat on the way. Add 20%, a rule of thumb, to cover that

      82,611.83×1.2=99,134.19 BTU/h
    11. Change to kilowatts (1 kW = 3,412.14 BTU/h)

      99,134.193,412.14=29.053 kW
    12. Electric heat turns all its power into heat. Round the watts up to the next 500 W to pick a size

      29,053 W → size=29,500 W electric heat
  6. 6. Heat needed (heater output): 28,150 BTU/h

    1. Change to feet and °F, the units the insulation values use (1 ft² = 0.09290304 m², 1 ft = 0.3048 m, 1 °C of difference = 1.8 °F)

      140 m²0.09290304=1,506.95 ft²
    2. Find how much warmer you want it inside than outside. This temperature rise drives every heat loss below

      21−(−11)×1.8=57.6 °F
    3. Picture the space as a square box. Its outside wall area is the distance around (4 × √area) times the height, times the 25% that faces outdoors

      4×1,506.95×5.9055×0.25=229.25 ft²
    4. Heat through the solid walls (85% of the wall area at R-4): area × temperature rise ÷ R-value

      194.86×57.64=2,806 BTU/h
    5. Heat through windows and doors (15% of the wall area at U-1): area × U-factor × temperature rise

      34.39×1×57.6=1,980.71 BTU/h
    6. Heat through the ceiling into the attic (R-11)

      1,506.95×57.611=7,890.92 BTU/h
    7. Heat carried off by air leaking in and out: 0.018 × volume × 1.5 air changes an hour × temperature rise

      0.018×8,899.3×1.5×57.6=13,840.19 BTU/h
    8. Heat lost through the edge of the slab: 0.73 BTU/h for each foot of outside edge and each degree (no edge insulation)

      0.73×38.82×57.6=1,632.28 BTU/h
    9. Add the parts to get the heat the house loses on a design-cold day

      2,806+1,980.71+7,890.92+13,840.19+1,632.28=28,150.1 BTU/h
    10. With no ducts, the heat goes straight into the room

      heat needed=28,150.1 BTU/h
    11. Change to kilowatts (1 kW = 3,412.14 BTU/h)

      28,150.13,412.14=8.25 kW
    12. Electric heat turns all its power into heat. Round the watts up to the next 500 W to pick a size

      8,250 W → size=8,500 W electric heat
  7. 7. Heat needed (heater output): 10,880 BTU/h

    1. Find how much warmer you want it inside than outside. This temperature rise drives every heat loss below

      66−12=54 °F
    2. Picture the space as a square box. Its outside wall area is the distance around (4 × √area) times the height

      4×1,400×8=1,197.33 ft²
    3. Heat through the solid walls (85% of the wall area at R-21): area × temperature rise ÷ R-value

      1,017.73×5421=2,617.02 BTU/h
    4. Heat through windows and doors (15% of the wall area at U-0.3): area × U-factor × temperature rise

      179.6×0.3×54=2,909.51 BTU/h
    5. Heat through the ceiling into the attic (R-49)

      1,400×5449=1,542.86 BTU/h
    6. Heat carried off by air leaking in and out: 0.018 × volume × 0.35 air changes an hour × temperature rise

      0.018×11,200×0.35×54=3,810.24 BTU/h
    7. Add the four parts. A heated space below loses no heat through the floor

      2,617.02+2,909.51+1,542.86+3,810.24=10,879.63 BTU/h
    8. The ducts are inside the heated space, so any heat they lose stays in the house

      heat needed=10,879.63 BTU/h
    9. Change to kilowatts (1 kW = 3,412.14 BTU/h)

      10,879.633,412.14=3.189 kW
    10. A furnace that is 80% efficient must burn more fuel than the heat it delivers, so divide by its efficiency

      10,879.630.8=13,599.54 BTU/h
    11. Round the input up to the next 10,000 BTU/h to pick a size

      size=20,000 BTU/h furnace (input)
  8. 8. Heat needed (heater output): 21,992 BTU/h

    1. Change to feet and °F, the units the insulation values use (1 ft² = 0.09290304 m², 1 ft = 0.3048 m, 1 °C of difference = 1.8 °F)

      120 m²0.09290304=1,291.67 ft²
    2. Find how much warmer you want it inside than outside. This temperature rise drives every heat loss below

      17−(−13)×1.8=54 °F
    3. Picture the space as a square box. Its outside wall area is the distance around (4 × √area) times the height, times the 50% that faces outdoors

      4×1,291.67×8.8583×0.5=636.73 ft²
    4. Heat through the solid walls (85% of the wall area at R-13): area × temperature rise ÷ R-value

      541.22×5413=2,248.14 BTU/h
    5. Heat through windows and doors (15% of the wall area at U-0.5): area × U-factor × temperature rise

      95.51×0.5×54=2,578.75 BTU/h
    6. Heat through the ceiling into the attic (R-30)

      1,291.67×5430=2,325 BTU/h
    7. Heat carried off by air leaking in and out: 0.018 × volume × 0.75 air changes an hour × temperature rise

      0.018×11,441.95×0.75×54=8,341.18 BTU/h
    8. Heat lost through the edge of the slab: 0.73 BTU/h for each foot of outside edge and each degree (no edge insulation)

      0.73×71.88×54=2,833.49 BTU/h
    9. Add the parts to get the heat the house loses on a design-cold day

      2,248.14+2,578.75+2,325+8,341.18+2,833.49=18,326.58 BTU/h
    10. Ducts in an unheated attic, crawlspace or garage leak and lose heat on the way. Add 20%, a rule of thumb, to cover that

      18,326.58×1.2=21,991.89 BTU/h
    11. Change to kilowatts (1 kW = 3,412.14 BTU/h)

      21,991.893,412.14=6.445 kW
    12. Electric heat turns all its power into heat. Round the watts up to the next 500 W to pick a size

      6,445 W → size=6,500 W electric heat
  9. 9. Heat needed (heater output): 7,888 BTU/h

    1. Find how much warmer you want it inside than outside. This temperature rise drives every heat loss below

      64−8=56 °F
    2. Picture the space as a square box. Its outside wall area is the distance around (4 × √area) times the height, times the 25% that faces outdoors

      4×1,500×7×0.25=271.11 ft²
    3. Heat through the solid walls (85% of the wall area at R-21): area × temperature rise ÷ R-value

      230.44×5621=614.51 BTU/h
    4. Heat through windows and doors (15% of the wall area at U-0.3): area × U-factor × temperature rise

      40.67×0.3×56=683.19 BTU/h
    5. Heat through the ceiling into the attic (R-49)

      1,500×5649=1,714.29 BTU/h
    6. Heat carried off by air leaking in and out: 0.018 × volume × 0.35 air changes an hour × temperature rise

      0.018×10,500×0.35×56=3,704.4 BTU/h
    7. Heat lost through the edge of the slab: 0.54 BTU/h for each foot of outside edge and each degree (insulated edge)

      0.54×38.73×56=1,171.19 BTU/h
    8. Add the parts to get the heat the house loses on a design-cold day

      614.51+683.19+1,714.29+3,704.4+1,171.19=7,887.58 BTU/h
    9. With no ducts, the heat goes straight into the room

      heat needed=7,887.58 BTU/h
    10. Change to kilowatts (1 kW = 3,412.14 BTU/h)

      7,887.583,412.14=2.312 kW
    11. A furnace that is 70% efficient must burn more fuel than the heat it delivers, so divide by its efficiency

      7,887.580.7=11,267.98 BTU/h
    12. Round the input up to the next 10,000 BTU/h to pick a size

      size=20,000 BTU/h furnace (input)
  10. 10. Heat needed (heater output): 7,790 BTU/h

    1. Find how much warmer you want it inside than outside. This temperature rise drives every heat loss below

      50−8=42 °F
    2. Picture the space as a square box. Its outside wall area is the distance around (4 × √area) times the height, times the 50% that faces outdoors

      4×1,800×8×0.5=678.82 ft²
    3. Heat through the solid walls (85% of the wall area at R-21): area × temperature rise ÷ R-value

      577×4221=1,154 BTU/h
    4. Heat through windows and doors (15% of the wall area at U-0.3): area × U-factor × temperature rise

      101.82×0.3×42=1,282.97 BTU/h
    5. Heat through the ceiling into the attic (R-49)

      1,800×4249=1,542.86 BTU/h
    6. Heat carried off by air leaking in and out: 0.018 × volume × 0.35 air changes an hour × temperature rise

      0.018×14,400×0.35×42=3,810.24 BTU/h
    7. Add the four parts. A heated space below loses no heat through the floor

      1,154+1,282.97+1,542.86+3,810.24=7,790.07 BTU/h
    8. The ducts are inside the heated space, so any heat they lose stays in the house

      heat needed=7,790.07 BTU/h
    9. Change to kilowatts (1 kW = 3,412.14 BTU/h)

      7,790.073,412.14=2.283 kW
    10. Electric heat turns all its power into heat. Round the watts up to the next 500 W to pick a size

      2,283 W → size=2,500 W electric heat