Heating BTU worksheet
Grades 6–7 · CCSS 6.EE.A.2.c
Calcapedia Solve each problem and show your work. Round answers to 2 decimal places where needed.
- 1.
Problem 1. - Units: Meters and °C
- Floor area to heat: 150 m²
- Ceiling height: 2 m
- Insulation and air sealing: Poor: older home, little insulation, single-pane windows, drafty
- Walls that face outdoors: About half (a corner room)
- What's under the floor: A heated basement or another heated floor
- Heating ducts: No ducts (space heater, baseboard or ductless)
- Indoor temperature you want: 17 °C
- Outdoor design temperature: -12 °C
- Heater type: Gas, propane or oil furnace
- Furnace efficiency (AFUE): 80%
Find: Heat needed (heater output)
Answer
- 2.
Problem 2. - Units: Feet and °F
- Floor area to heat: 1,800 ft²
- Ceiling height: 7 ft
- Insulation and air sealing: Poor: older home, little insulation, single-pane windows, drafty
- Walls that face outdoors: About half (a corner room)
- What's under the floor: An unheated crawlspace or basement
- Heating ducts: No ducts (space heater, baseboard or ductless)
- Indoor temperature you want: 55 °F
- Outdoor design temperature: 8 °F
- Heater type: Gas, propane or oil furnace
- Furnace efficiency (AFUE): 100%
Find: Heat needed (heater output)
Answer
- 3.
Problem 3. - Units: Meters and °C
- Floor area to heat: 200 m²
- Ceiling height: 2 m
- Insulation and air sealing: Average: insulated walls and attic, double-pane windows
- Walls that face outdoors: All of them (a whole house or a detached space)
- What's under the floor: A heated basement or another heated floor
- Heating ducts: No ducts (space heater, baseboard or ductless)
- Indoor temperature you want: 28 °C
- Outdoor design temperature: -13 °C
- Heater type: Electric heater (100% efficient)
Find: Heat needed (heater output)
Answer
- 4.
Problem 4. - Units: Meters and °C
- Floor area to heat: 152 m²
- Ceiling height: 2.8 m
- Insulation and air sealing: Poor: older home, little insulation, single-pane windows, drafty
- Walls that face outdoors: About half (a corner room)
- What's under the floor: A concrete slab on the ground
- Heating ducts: Ducts inside the heated space
- Indoor temperature you want: 21 °C
- Outdoor design temperature: -12 °C
- Heater type: Gas, propane or oil furnace
- Furnace efficiency (AFUE): 65%
Find: Heat needed (heater output)
Answer
- 5.
Problem 5. - Units: Meters and °C
- Floor area to heat: 180 m²
- Ceiling height: 2.8 m
- Insulation and air sealing: Poor: older home, little insulation, single-pane windows, drafty
- Walls that face outdoors: About half (a corner room)
- What's under the floor: An unheated crawlspace or basement
- Heating ducts: Ducts in an unheated attic, crawlspace or garage (+20%)
- Indoor temperature you want: 24 °C
- Outdoor design temperature: -8 °C
- Heater type: Electric heater (100% efficient)
Find: Heat needed (heater output)
Answer
- 6.
Problem 6. - Units: Meters and °C
- Floor area to heat: 140 m²
- Ceiling height: 1.8 m
- Insulation and air sealing: Poor: older home, little insulation, single-pane windows, drafty
- Walls that face outdoors: About a quarter (a room with one outside wall)
- What's under the floor: A concrete slab on the ground
- Heating ducts: No ducts (space heater, baseboard or ductless)
- Indoor temperature you want: 21 °C
- Outdoor design temperature: -11 °C
- Heater type: Electric heater (100% efficient)
Find: Heat needed (heater output)
Answer
- 7.
Problem 7. - Units: Feet and °F
- Floor area to heat: 1,400 ft²
- Ceiling height: 8 ft
- Insulation and air sealing: Good: newer, well insulated and sealed, low-e windows
- Walls that face outdoors: All of them (a whole house or a detached space)
- What's under the floor: A heated basement or another heated floor
- Heating ducts: Ducts inside the heated space
- Indoor temperature you want: 66 °F
- Outdoor design temperature: 12 °F
- Heater type: Gas, propane or oil furnace
- Furnace efficiency (AFUE): 80%
Find: Heat needed (heater output)
Answer
- 8.
Problem 8. - Units: Meters and °C
- Floor area to heat: 120 m²
- Ceiling height: 2.7 m
- Insulation and air sealing: Average: insulated walls and attic, double-pane windows
- Walls that face outdoors: About half (a corner room)
- What's under the floor: A concrete slab on the ground
- Heating ducts: Ducts in an unheated attic, crawlspace or garage (+20%)
- Indoor temperature you want: 17 °C
- Outdoor design temperature: -13 °C
- Heater type: Electric heater (100% efficient)
Find: Heat needed (heater output)
Answer
- 9.
Problem 9. - Units: Feet and °F
- Floor area to heat: 1,500 ft²
- Ceiling height: 7 ft
- Insulation and air sealing: Good: newer, well insulated and sealed, low-e windows
- Walls that face outdoors: About a quarter (a room with one outside wall)
- What's under the floor: A concrete slab on the ground
- Heating ducts: No ducts (space heater, baseboard or ductless)
- Indoor temperature you want: 64 °F
- Outdoor design temperature: 8 °F
- Heater type: Gas, propane or oil furnace
- Furnace efficiency (AFUE): 70%
Find: Heat needed (heater output)
Answer
- 10.
Problem 10. - Units: Feet and °F
- Floor area to heat: 1,800 ft²
- Ceiling height: 8 ft
- Insulation and air sealing: Good: newer, well insulated and sealed, low-e windows
- Walls that face outdoors: About half (a corner room)
- What's under the floor: A heated basement or another heated floor
- Heating ducts: Ducts inside the heated space
- Indoor temperature you want: 50 °F
- Outdoor design temperature: 8 °F
- Heater type: Electric heater (100% efficient)
Find: Heat needed (heater output)
Answer
Answer key: Heating BTU worksheet
Calcapedia 1. Heat needed (heater output): 32,572 BTU/h
Change to feet and °F, the units the insulation values use (1 ft² = 0.09290304 m², 1 ft = 0.3048 m, 1 °C of difference = 1.8 °F)
Find how much warmer you want it inside than outside. This temperature rise drives every heat loss below
Picture the space as a square box. Its outside wall area is the distance around (4 × √area) times the height, times the 50% that faces outdoors
Heat through the solid walls (85% of the wall area at R-4): area × temperature rise ÷ R-value
Heat through windows and doors (15% of the wall area at U-1): area × U-factor × temperature rise
Heat through the ceiling into the attic (R-11)
Heat carried off by air leaking in and out: 0.018 × volume × 1.5 air changes an hour × temperature rise
Add the four parts. A heated space below loses no heat through the floor
With no ducts, the heat goes straight into the room
Change to kilowatts (1 kW = 3,412.14 BTU/h)
A furnace that is 80% efficient must burn more fuel than the heat it delivers, so divide by its efficiency
Round the input up to the next 10,000 BTU/h to pick a size
2. Heat needed (heater output): 54,950 BTU/h
Find how much warmer you want it inside than outside. This temperature rise drives every heat loss below
Picture the space as a square box. Its outside wall area is the distance around (4 × √area) times the height, times the 50% that faces outdoors
Heat through the solid walls (85% of the wall area at R-4): area × temperature rise ÷ R-value
Heat through windows and doors (15% of the wall area at U-1): area × U-factor × temperature rise
Heat through the ceiling into the attic (R-11)
Heat carried off by air leaking in and out: 0.018 × volume × 1.5 air changes an hour × temperature rise
Heat lost down through the floor (R-4). The full temperature rise is used, because a vented crawlspace can get nearly as cold as outdoors
Add the parts to get the heat the house loses on a design-cold day
With no ducts, the heat goes straight into the room
Change to kilowatts (1 kW = 3,412.14 BTU/h)
A furnace that is 100% efficient must burn more fuel than the heat it delivers, so divide by its efficiency
Round the input up to the next 10,000 BTU/h to pick a size
3. Heat needed (heater output): 31,986 BTU/h
Change to feet and °F, the units the insulation values use (1 ft² = 0.09290304 m², 1 ft = 0.3048 m, 1 °C of difference = 1.8 °F)
Find how much warmer you want it inside than outside. This temperature rise drives every heat loss below
Picture the space as a square box. Its outside wall area is the distance around (4 × √area) times the height
Heat through the solid walls (85% of the wall area at R-13): area × temperature rise ÷ R-value
Heat through windows and doors (15% of the wall area at U-0.5): area × U-factor × temperature rise
Heat through the ceiling into the attic (R-30)
Heat carried off by air leaking in and out: 0.018 × volume × 0.75 air changes an hour × temperature rise
Add the four parts. A heated space below loses no heat through the floor
With no ducts, the heat goes straight into the room
Change to kilowatts (1 kW = 3,412.14 BTU/h)
Electric heat turns all its power into heat. Round the watts up to the next 500 W to pick a size
4. Heat needed (heater output): 52,450 BTU/h
Change to feet and °F, the units the insulation values use (1 ft² = 0.09290304 m², 1 ft = 0.3048 m, 1 °C of difference = 1.8 °F)
Find how much warmer you want it inside than outside. This temperature rise drives every heat loss below
Picture the space as a square box. Its outside wall area is the distance around (4 × √area) times the height, times the 50% that faces outdoors
Heat through the solid walls (85% of the wall area at R-4): area × temperature rise ÷ R-value
Heat through windows and doors (15% of the wall area at U-1): area × U-factor × temperature rise
Heat through the ceiling into the attic (R-11)
Heat carried off by air leaking in and out: 0.018 × volume × 1.5 air changes an hour × temperature rise
Heat lost through the edge of the slab: 0.73 BTU/h for each foot of outside edge and each degree (no edge insulation)
Add the parts to get the heat the house loses on a design-cold day
The ducts are inside the heated space, so any heat they lose stays in the house
Change to kilowatts (1 kW = 3,412.14 BTU/h)
A furnace that is 65% efficient must burn more fuel than the heat it delivers, so divide by its efficiency
Round the input up to the next 10,000 BTU/h to pick a size
5. Heat needed (heater output): 99,134 BTU/h
Change to feet and °F, the units the insulation values use (1 ft² = 0.09290304 m², 1 ft = 0.3048 m, 1 °C of difference = 1.8 °F)
Find how much warmer you want it inside than outside. This temperature rise drives every heat loss below
Picture the space as a square box. Its outside wall area is the distance around (4 × √area) times the height, times the 50% that faces outdoors
Heat through the solid walls (85% of the wall area at R-4): area × temperature rise ÷ R-value
Heat through windows and doors (15% of the wall area at U-1): area × U-factor × temperature rise
Heat through the ceiling into the attic (R-11)
Heat carried off by air leaking in and out: 0.018 × volume × 1.5 air changes an hour × temperature rise
Heat lost down through the floor (R-4). The full temperature rise is used, because a vented crawlspace can get nearly as cold as outdoors
Add the parts to get the heat the house loses on a design-cold day
Ducts in an unheated attic, crawlspace or garage leak and lose heat on the way. Add 20%, a rule of thumb, to cover that
Change to kilowatts (1 kW = 3,412.14 BTU/h)
Electric heat turns all its power into heat. Round the watts up to the next 500 W to pick a size
6. Heat needed (heater output): 28,150 BTU/h
Change to feet and °F, the units the insulation values use (1 ft² = 0.09290304 m², 1 ft = 0.3048 m, 1 °C of difference = 1.8 °F)
Find how much warmer you want it inside than outside. This temperature rise drives every heat loss below
Picture the space as a square box. Its outside wall area is the distance around (4 × √area) times the height, times the 25% that faces outdoors
Heat through the solid walls (85% of the wall area at R-4): area × temperature rise ÷ R-value
Heat through windows and doors (15% of the wall area at U-1): area × U-factor × temperature rise
Heat through the ceiling into the attic (R-11)
Heat carried off by air leaking in and out: 0.018 × volume × 1.5 air changes an hour × temperature rise
Heat lost through the edge of the slab: 0.73 BTU/h for each foot of outside edge and each degree (no edge insulation)
Add the parts to get the heat the house loses on a design-cold day
With no ducts, the heat goes straight into the room
Change to kilowatts (1 kW = 3,412.14 BTU/h)
Electric heat turns all its power into heat. Round the watts up to the next 500 W to pick a size
7. Heat needed (heater output): 10,880 BTU/h
Find how much warmer you want it inside than outside. This temperature rise drives every heat loss below
Picture the space as a square box. Its outside wall area is the distance around (4 × √area) times the height
Heat through the solid walls (85% of the wall area at R-21): area × temperature rise ÷ R-value
Heat through windows and doors (15% of the wall area at U-0.3): area × U-factor × temperature rise
Heat through the ceiling into the attic (R-49)
Heat carried off by air leaking in and out: 0.018 × volume × 0.35 air changes an hour × temperature rise
Add the four parts. A heated space below loses no heat through the floor
The ducts are inside the heated space, so any heat they lose stays in the house
Change to kilowatts (1 kW = 3,412.14 BTU/h)
A furnace that is 80% efficient must burn more fuel than the heat it delivers, so divide by its efficiency
Round the input up to the next 10,000 BTU/h to pick a size
8. Heat needed (heater output): 21,992 BTU/h
Change to feet and °F, the units the insulation values use (1 ft² = 0.09290304 m², 1 ft = 0.3048 m, 1 °C of difference = 1.8 °F)
Find how much warmer you want it inside than outside. This temperature rise drives every heat loss below
Picture the space as a square box. Its outside wall area is the distance around (4 × √area) times the height, times the 50% that faces outdoors
Heat through the solid walls (85% of the wall area at R-13): area × temperature rise ÷ R-value
Heat through windows and doors (15% of the wall area at U-0.5): area × U-factor × temperature rise
Heat through the ceiling into the attic (R-30)
Heat carried off by air leaking in and out: 0.018 × volume × 0.75 air changes an hour × temperature rise
Heat lost through the edge of the slab: 0.73 BTU/h for each foot of outside edge and each degree (no edge insulation)
Add the parts to get the heat the house loses on a design-cold day
Ducts in an unheated attic, crawlspace or garage leak and lose heat on the way. Add 20%, a rule of thumb, to cover that
Change to kilowatts (1 kW = 3,412.14 BTU/h)
Electric heat turns all its power into heat. Round the watts up to the next 500 W to pick a size
9. Heat needed (heater output): 7,888 BTU/h
Find how much warmer you want it inside than outside. This temperature rise drives every heat loss below
Picture the space as a square box. Its outside wall area is the distance around (4 × √area) times the height, times the 25% that faces outdoors
Heat through the solid walls (85% of the wall area at R-21): area × temperature rise ÷ R-value
Heat through windows and doors (15% of the wall area at U-0.3): area × U-factor × temperature rise
Heat through the ceiling into the attic (R-49)
Heat carried off by air leaking in and out: 0.018 × volume × 0.35 air changes an hour × temperature rise
Heat lost through the edge of the slab: 0.54 BTU/h for each foot of outside edge and each degree (insulated edge)
Add the parts to get the heat the house loses on a design-cold day
With no ducts, the heat goes straight into the room
Change to kilowatts (1 kW = 3,412.14 BTU/h)
A furnace that is 70% efficient must burn more fuel than the heat it delivers, so divide by its efficiency
Round the input up to the next 10,000 BTU/h to pick a size
10. Heat needed (heater output): 7,790 BTU/h
Find how much warmer you want it inside than outside. This temperature rise drives every heat loss below
Picture the space as a square box. Its outside wall area is the distance around (4 × √area) times the height, times the 50% that faces outdoors
Heat through the solid walls (85% of the wall area at R-21): area × temperature rise ÷ R-value
Heat through windows and doors (15% of the wall area at U-0.3): area × U-factor × temperature rise
Heat through the ceiling into the attic (R-49)
Heat carried off by air leaking in and out: 0.018 × volume × 0.35 air changes an hour × temperature rise
Add the four parts. A heated space below loses no heat through the floor
The ducts are inside the heated space, so any heat they lose stays in the house
Change to kilowatts (1 kW = 3,412.14 BTU/h)
Electric heat turns all its power into heat. Round the watts up to the next 500 W to pick a size