Power Factor worksheet

Grade 12 to college · CCSS HSG.SRT.C.8

Solve each problem and show your work. Round answers to 2 decimal places where needed.

  1. Problem 1.
    • Values you know: Real power and power factor
    • Power units: kW, kVAR, kVA
    • Real power (P): 56
    • Power factor: 0.9
    • Target power factor (optional): 0.8

    Find: Apparent power (S)

  2. Problem 2.
    • Values you know: Real power and reactive power
    • Power units: kW, kVAR, kVA
    • Real power (P): 32
    • Reactive power (Q): 20
    • Target power factor (optional): 1

    Find: Power factor

  3. Problem 3.
    • Values you know: Real power and power factor
    • Power units: W, VAR, VA
    • Real power (P): 45
    • Power factor: 1
    • Target power factor (optional): 0.76

    Find: Apparent power (S)

  4. Problem 4.
    • Values you know: Real power and apparent power
    • Power units: W, VAR, VA
    • Real power (P): 33
    • Apparent power (S): 55
    • Target power factor (optional): 0.9

    Find: Power factor

  5. Problem 5.
    • Values you know: Apparent power and power factor
    • Power units: W, VAR, VA
    • Apparent power (S): 70
    • Power factor: 0.7
    • Target power factor (optional): 0.95

    Find: Real power (P)

  6. Problem 6.
    • Values you know: Voltage, current and real power (single-phase)
    • Power units: kW, kVAR, kVA
    • Real power (P): 43
    • Voltage (RMS): 280 V
    • Current (RMS): 200 A
    • Target power factor (optional): 0.95

    Find: Power factor

  7. Problem 7.
    • Values you know: Real power and apparent power
    • Power units: kW, kVAR, kVA
    • Real power (P): 42
    • Apparent power (S): 45
    • Target power factor (optional): 0.55

    Find: Power factor

  8. Problem 8.
    • Values you know: Real power and reactive power
    • Power units: W, VAR, VA
    • Real power (P): 36
    • Reactive power (Q): 34
    • Target power factor (optional): 0.8

    Find: Power factor

  9. Problem 9.
    • Values you know: Apparent power and power factor
    • Power units: kW, kVAR, kVA
    • Apparent power (S): 70
    • Power factor: 0.6
    • Target power factor (optional): 0.6

    Find: Real power (P)

  10. Problem 10.
    • Values you know: Real power and reactive power
    • Power units: kW, kVAR, kVA
    • Real power (P): 38
    • Reactive power (Q): 32
    • Target power factor (optional): 1

    Find: Power factor

Answer key: Power Factor worksheet

  1. 1. Apparent power (S): 62.22 kVA

    1. Find the apparent power S: divide the real power by the power factor

      S=560.9=62.2222222222 kVA
    2. Find the reactive power Q. The three powers form a right triangle, so Q is the leftover side

      Q=62.22222222222−562=27.1220378709 kVAR
    3. Find the phase angle φ, how far the current lags behind the voltage. Its cosine is the power factor

      φ=arccos(0.9)=25.8419327632 °
  2. 2. Power factor: 0.848

    1. Find the apparent power S. The three powers form a right triangle, so S is the long side

      S=322+202=37.7359245282 kVA
    2. Find the power factor (PF): divide the real power P, which does the work, by the apparent power S

      PF=3237.7359245282=0.847998304
    3. Find the phase angle φ, how far the current lags behind the voltage. Its cosine is the power factor

      φ=arccos(0.847998304)=32.0053832081 °
    4. Size the capacitor (Qc) to raise the power factor to 1. It must supply the reactive power you no longer want from the grid: the angle now (φ₁) versus the target angle (φ₂ = arccos(1) = 0°)

      Qc=32×(0.625−0)=20 kVAR
    5. Find the apparent power after correction (S₂): the same real power divided by the target power factor

      S₂=321=32 kVA
  3. 3. Apparent power (S): 45 VA

    1. Find the apparent power S: divide the real power by the power factor

      S=451=45 VA
    2. Find the reactive power Q. The three powers form a right triangle, so Q is the leftover side

      Q=452−452=0 VAR
    3. Find the phase angle φ, how far the current lags behind the voltage. Its cosine is the power factor

      φ=arccos(1)=0 °
  4. 4. Power factor: 0.6

    1. Find the power factor (PF): divide the real power P, which does the work, by the apparent power S

      PF=3355=0.6
    2. Find the reactive power Q. The three powers form a right triangle, so Q is the leftover side

      Q=552−332=44 VAR
    3. Find the phase angle φ, how far the current lags behind the voltage. Its cosine is the power factor

      φ=arccos(0.6)=53.1301023542 °
    4. Size the capacitor (Qc) to raise the power factor to 0.9. It must supply the reactive power you no longer want from the grid: the angle now (φ₁) versus the target angle (φ₂ = arccos(0.9) = 25.8419°)

      Qc=33×(1.33333333−0.4843221)=28.0173705404 VAR
    5. Find the apparent power after correction (S₂): the same real power divided by the target power factor

      S₂=330.9=36.6666666667 VA
  5. 5. Real power (P): 49 W

    1. Find the real power P: multiply the apparent power by the power factor

      P=70×0.7=49 W
    2. Find the reactive power Q. The three powers form a right triangle, so Q is the leftover side

      Q=702−492=49.9899989998 VAR
    3. Find the phase angle φ, how far the current lags behind the voltage. Its cosine is the power factor

      φ=arccos(0.7)=45.5729959992 °
    4. Size the capacitor (Qc) to raise the power factor to 0.95. It must supply the reactive power you no longer want from the grid: the angle now (φ₁) versus the target angle (φ₂ = arccos(0.95) = 18.1949°)

      Qc=49×(1.02020406−0.32868411)=33.884477846 VAR
    5. Find the apparent power after correction (S₂): the same real power divided by the target power factor

      S₂=490.95=51.5789473684 VA
  6. 6. Power factor: 0.7679

    1. Find the apparent power S: multiply volts by amps, then divide by 1000 to get kVA

      S=280×2001,000=56 kVA
    2. Find the power factor (PF): divide the real power P, which does the work, by the apparent power S

      PF=4356=0.7678571429
    3. Find the reactive power Q. The three powers form a right triangle, so Q is the leftover side

      Q=562−432=35.8747822293 kVAR
    4. Find the phase angle φ, how far the current lags behind the voltage. Its cosine is the power factor

      φ=arccos(0.7678571429)=39.8381498056 °
    5. Size the capacitor (Qc) to raise the power factor to 0.95. It must supply the reactive power you no longer want from the grid: the angle now (φ₁) versus the target angle (φ₂ = arccos(0.95) = 18.1949°)

      Qc=43×(0.83429726−0.32868411)=21.7413657066 kVAR
    6. Find the apparent power after correction (S₂): the same real power divided by the target power factor

      S₂=430.95=45.2631578947 kVA
  7. 7. Power factor: 0.9333

    1. Find the power factor (PF): divide the real power P, which does the work, by the apparent power S

      PF=4245=0.9333333333
    2. Find the reactive power Q. The three powers form a right triangle, so Q is the leftover side

      Q=452−422=16.1554944214 kVAR
    3. Find the phase angle φ, how far the current lags behind the voltage. Its cosine is the power factor

      φ=arccos(0.9333333333)=21.0394697813 °
  8. 8. Power factor: 0.727

    1. Find the apparent power S. The three powers form a right triangle, so S is the long side

      S=362+342=49.5176736126 VA
    2. Find the power factor (PF): divide the real power P, which does the work, by the apparent power S

      PF=3649.5176736126=0.7270131525
    3. Find the phase angle φ, how far the current lags behind the voltage. Its cosine is the power factor

      φ=arccos(0.7270131525)=43.3634229584 °
    4. Size the capacitor (Qc) to raise the power factor to 0.8. It must supply the reactive power you no longer want from the grid: the angle now (φ₁) versus the target angle (φ₂ = arccos(0.8) = 36.8699°)

      Qc=36×(0.94444444−0.75)=7 VAR
    5. Find the apparent power after correction (S₂): the same real power divided by the target power factor

      S₂=360.8=45 VA
  9. 9. Real power (P): 42 kW

    1. Find the real power P: multiply the apparent power by the power factor

      P=70×0.6=42 kW
    2. Find the reactive power Q. The three powers form a right triangle, so Q is the leftover side

      Q=702−422=56 kVAR
    3. Find the phase angle φ, how far the current lags behind the voltage. Its cosine is the power factor

      φ=arccos(0.6)=53.1301023542 °
  10. 10. Power factor: 0.7649

    1. Find the apparent power S. The three powers form a right triangle, so S is the long side

      S=382+322=49.6789693935 kVA
    2. Find the power factor (PF): divide the real power P, which does the work, by the apparent power S

      PF=3849.6789693935=0.7649111981
    3. Find the phase angle φ, how far the current lags behind the voltage. Its cosine is the power factor

      φ=arccos(0.7649111981)=40.1009075462 °
    4. Size the capacitor (Qc) to raise the power factor to 1. It must supply the reactive power you no longer want from the grid: the angle now (φ₁) versus the target angle (φ₂ = arccos(1) = 0°)

      Qc=38×(0.84210526−0)=32 kVAR
    5. Find the apparent power after correction (S₂): the same real power divided by the target power factor

      S₂=381=38 kVA