Find the apparent power S: divide the real power by the power factor
Find the reactive power Q. The three powers form a right triangle, so Q is the leftover side
Find the phase angle φ, how far the current lags behind the voltage. Its cosine is the power factor
2. Power factor: 0.848
Find the apparent power S. The three powers form a right triangle, so S is the long side
Find the power factor (PF): divide the real power P, which does the work, by the apparent power S
Find the phase angle φ, how far the current lags behind the voltage. Its cosine is the power factor
Size the capacitor (Qc) to raise the power factor to 1. It must supply the reactive power you no longer want from the grid: the angle now (φ₁) versus the target angle (φ₂ = arccos(1) = 0°)
Find the apparent power after correction (S₂): the same real power divided by the target power factor
3. Apparent power (S): 45 VA
Find the apparent power S: divide the real power by the power factor
Find the reactive power Q. The three powers form a right triangle, so Q is the leftover side
Find the phase angle φ, how far the current lags behind the voltage. Its cosine is the power factor
4. Power factor: 0.6
Find the power factor (PF): divide the real power P, which does the work, by the apparent power S
Find the reactive power Q. The three powers form a right triangle, so Q is the leftover side
Find the phase angle φ, how far the current lags behind the voltage. Its cosine is the power factor
Size the capacitor (Qc) to raise the power factor to 0.9. It must supply the reactive power you no longer want from the grid: the angle now (φ₁) versus the target angle (φ₂ = arccos(0.9) = 25.8419°)
Find the apparent power after correction (S₂): the same real power divided by the target power factor
5. Real power (P): 49 W
Find the real power P: multiply the apparent power by the power factor
Find the reactive power Q. The three powers form a right triangle, so Q is the leftover side
Find the phase angle φ, how far the current lags behind the voltage. Its cosine is the power factor
Size the capacitor (Qc) to raise the power factor to 0.95. It must supply the reactive power you no longer want from the grid: the angle now (φ₁) versus the target angle (φ₂ = arccos(0.95) = 18.1949°)
Find the apparent power after correction (S₂): the same real power divided by the target power factor
6. Power factor: 0.7679
Find the apparent power S: multiply volts by amps, then divide by 1000 to get kVA
Find the power factor (PF): divide the real power P, which does the work, by the apparent power S
Find the reactive power Q. The three powers form a right triangle, so Q is the leftover side
Find the phase angle φ, how far the current lags behind the voltage. Its cosine is the power factor
Size the capacitor (Qc) to raise the power factor to 0.95. It must supply the reactive power you no longer want from the grid: the angle now (φ₁) versus the target angle (φ₂ = arccos(0.95) = 18.1949°)
Find the apparent power after correction (S₂): the same real power divided by the target power factor
7. Power factor: 0.9333
Find the power factor (PF): divide the real power P, which does the work, by the apparent power S
Find the reactive power Q. The three powers form a right triangle, so Q is the leftover side
Find the phase angle φ, how far the current lags behind the voltage. Its cosine is the power factor
8. Power factor: 0.727
Find the apparent power S. The three powers form a right triangle, so S is the long side
Find the power factor (PF): divide the real power P, which does the work, by the apparent power S
Find the phase angle φ, how far the current lags behind the voltage. Its cosine is the power factor
Size the capacitor (Qc) to raise the power factor to 0.8. It must supply the reactive power you no longer want from the grid: the angle now (φ₁) versus the target angle (φ₂ = arccos(0.8) = 36.8699°)
Find the apparent power after correction (S₂): the same real power divided by the target power factor
9. Real power (P): 42 kW
Find the real power P: multiply the apparent power by the power factor
Find the reactive power Q. The three powers form a right triangle, so Q is the leftover side
Find the phase angle φ, how far the current lags behind the voltage. Its cosine is the power factor
10. Power factor: 0.7649
Find the apparent power S. The three powers form a right triangle, so S is the long side
Find the power factor (PF): divide the real power P, which does the work, by the apparent power S
Find the phase angle φ, how far the current lags behind the voltage. Its cosine is the power factor
Size the capacitor (Qc) to raise the power factor to 1. It must supply the reactive power you no longer want from the grid: the angle now (φ₁) versus the target angle (φ₂ = arccos(1) = 0°)
Find the apparent power after correction (S₂): the same real power divided by the target power factor