Voltage Drop worksheet

Grades 11–12

Solve each problem and show your work. Round answers to 2 decimal places where needed.

  1. Problem 1.
    • Circuit type: Single-phase AC
    • Conductor: Copper
    • Wire size given as: Cross-sectional area
    • Conductor area: 3.2 mm²
    • One-way length of the run: 130 ft
    • Load current: 13 A
    • Source voltage: 90 V

    Find: Voltage drop

  2. Problem 2.
    • Circuit type: Three-phase AC
    • Conductor: Copper
    • Wire size given as: AWG gauge
    • Wire gauge: 000 (3/0) AWG
    • One-way length of the run: 115 ft
    • Load current: 15 A
    • Source voltage: 110 V

    Find: Voltage drop

  3. Problem 3.
    • Circuit type: Three-phase AC
    • Conductor: Copper
    • Wire size given as: Cross-sectional area
    • Conductor area: 2 mm²
    • One-way length of the run: 100 ft
    • Load current: 12 A
    • Source voltage: 140 V

    Find: Voltage drop

  4. Problem 4.
    • Circuit type: DC
    • Conductor: Aluminum
    • Wire size given as: Cross-sectional area
    • Conductor area: 3.6 mm²
    • One-way length of the run: 90 ft
    • Load current: 16 A
    • Source voltage: 120 V

    Find: Voltage drop

  5. Problem 5.
    • Circuit type: DC
    • Conductor: Aluminum
    • Wire size given as: AWG gauge
    • Wire gauge: 14 AWG
    • One-way length of the run: 80 ft
    • Load current: 13 A
    • Source voltage: 110 V

    Find: Voltage drop

  6. Problem 6.
    • Circuit type: Three-phase AC
    • Conductor: Copper
    • Wire size given as: AWG gauge
    • Wire gauge: 25 AWG
    • One-way length of the run: 85 ft
    • Load current: 13 A
    • Source voltage: 105 V

    Find: Voltage drop

  7. Problem 7.
    • Circuit type: Three-phase AC
    • Conductor: Copper
    • Wire size given as: Cross-sectional area
    • Conductor area: 2.8 mm²
    • One-way length of the run: 90 ft
    • Load current: 14 A
    • Source voltage: 134 V

    Find: Voltage drop

  8. Problem 8.
    • Circuit type: DC
    • Conductor: Copper
    • Wire size given as: Cross-sectional area
    • Conductor area: 2.4 mm²
    • One-way length of the run: 125 ft
    • Load current: 12 A
    • Source voltage: 145 V

    Find: Voltage drop

  9. Problem 9.
    • Circuit type: DC
    • Conductor: Copper
    • Wire size given as: Cross-sectional area
    • Conductor area: 1.8 mm²
    • One-way length of the run: 110 ft
    • Load current: 14 A
    • Source voltage: 125 V

    Find: Voltage drop

  10. Problem 10.
    • Circuit type: Single-phase AC
    • Conductor: Aluminum
    • Wire size given as: AWG gauge
    • Wire gauge: 11 AWG
    • One-way length of the run: 120 ft
    • Load current: 12 A
    • Source voltage: 130 V

    Find: Voltage drop

Answer key: Voltage Drop worksheet

  1. 1. Voltage drop: 5.55 V

    1. Resistance per meter of copper at 20 °C: divide the metal's resistivity ρ (how strongly it resists current, 1.724e-8 Ω·m or 0.01724 Ω·mm²/m) by the area

      R/m=0.017243.2=0.0053875 Ω/m
    2. Change the length to meters to match the resistance per meter (1 ft = 0.3048 m)

      130 ft×0.3048=39.624 m
    3. The current flows out and back, so the drop covers twice the one-way length: 2 × length × resistance per meter × current

      Vd=2×39.624×0.0053875×13=5.550332 V
    4. Divide the drop by the source voltage to see what share of it is lost, as a percent

      5.55033290×100=6.167%
    5. Take the drop away from the source voltage to get what is left at the load

      90−5.550332=84.449668 V
  2. 2. Voltage drop: 0.18 V

    1. Find the wire's thickness (diameter d) from its gauge number n = -2, using the standard AWG formula

      d=0.127×92(36−(−2)39)=10.404902 mm
    2. Work out the area of the round wire's cut end (A). A bigger area means less resistance

      A=π4×10.4049022=85.028773 mm²
    3. Resistance per meter of copper at 20 °C: divide the metal's resistivity ρ (how strongly it resists current, 1.724e-8 Ω·m or 0.01724 Ω·mm²/m) by the area

      R/m=0.0172485.028773=0.00020275 Ω/m
    4. Change the length to meters to match the resistance per meter (1 ft = 0.3048 m)

      115 ft×0.3048=35.052 m
    5. Three-phase drop between two lines: multiply √3 × length × resistance per meter × current

      Vd=3×35.052×0.00020275×15=0.184644 V
    6. Divide the drop by the source voltage to see what share of it is lost, as a percent

      0.184644110×100=0.1679%
    7. Take the drop away from the source voltage to get what is left at the load

      110−0.184644=109.815356 V
  3. 3. Voltage drop: 5.46 V

    1. Resistance per meter of copper at 20 °C: divide the metal's resistivity ρ (how strongly it resists current, 1.724e-8 Ω·m or 0.01724 Ω·mm²/m) by the area

      R/m=0.017242=0.00862 Ω/m
    2. Change the length to meters to match the resistance per meter (1 ft = 0.3048 m)

      100 ft×0.3048=30.48 m
    3. Three-phase drop between two lines: multiply √3 × length × resistance per meter × current

      Vd=3×30.48×0.00862×12=5.460898 V
    4. Divide the drop by the source voltage to see what share of it is lost, as a percent

      5.460898140×100=3.9006%
    5. Take the drop away from the source voltage to get what is left at the load

      140−5.460898=134.539102 V
  4. 4. Voltage drop: 6.88 V

    1. Resistance per meter of aluminum at 20 °C: divide the metal's resistivity ρ (how strongly it resists current, 2.82e-8 Ω·m or 0.0282 Ω·mm²/m) by the area

      R/m=0.02823.6=0.00783333 Ω/m
    2. Change the length to meters to match the resistance per meter (1 ft = 0.3048 m)

      90 ft×0.3048=27.432 m
    3. The current flows out and back, so the drop covers twice the one-way length: 2 × length × resistance per meter × current

      Vd=2×27.432×0.00783333×16=6.876288 V
    4. Divide the drop by the source voltage to see what share of it is lost, as a percent

      6.876288120×100=5.7302%
    5. Take the drop away from the source voltage to get what is left at the load

      120−6.876288=113.123712 V
  5. 5. Voltage drop: 8.59 V

    1. Find the wire's thickness (diameter d) from its gauge number n = 14, using the standard AWG formula

      d=0.127×92(36−1439)=1.627727 mm
    2. Work out the area of the round wire's cut end (A). A bigger area means less resistance

      A=π4×1.6277272=2.080908 mm²
    3. Resistance per meter of aluminum at 20 °C: divide the metal's resistivity ρ (how strongly it resists current, 2.82e-8 Ω·m or 0.0282 Ω·mm²/m) by the area

      R/m=0.02822.080908=0.01355178 Ω/m
    4. Change the length to meters to match the resistance per meter (1 ft = 0.3048 m)

      80 ft×0.3048=24.384 m
    5. The current flows out and back, so the drop covers twice the one-way length: 2 × length × resistance per meter × current

      Vd=2×24.384×0.01355178×13=8.591611 V
    6. Divide the drop by the source voltage to see what share of it is lost, as a percent

      8.591611110×100=7.8106%
    7. Take the drop away from the source voltage to get what is left at the load

      110−8.591611=101.408389 V
  6. 6. Voltage drop: 61.94 V

    1. Find the wire's thickness (diameter d) from its gauge number n = 25, using the standard AWG formula

      d=0.127×92(36−2539)=0.454666 mm
    2. Work out the area of the round wire's cut end (A). A bigger area means less resistance

      A=π4×0.4546662=0.162359 mm²
    3. Resistance per meter of copper at 20 °C: divide the metal's resistivity ρ (how strongly it resists current, 1.724e-8 Ω·m or 0.01724 Ω·mm²/m) by the area

      R/m=0.017240.162359=0.10618476 Ω/m
    4. Change the length to meters to match the resistance per meter (1 ft = 0.3048 m)

      85 ft×0.3048=25.908 m
    5. Three-phase drop between two lines: multiply √3 × length × resistance per meter × current

      Vd=3×25.908×0.10618476×13=61.944116 V
    6. Divide the drop by the source voltage to see what share of it is lost, as a percent

      61.944116105×100=58.9944%
    7. Take the drop away from the source voltage to get what is left at the load

      105−61.944116=43.055884 V
  7. 7. Voltage drop: 4.1 V

    1. Resistance per meter of copper at 20 °C: divide the metal's resistivity ρ (how strongly it resists current, 1.724e-8 Ω·m or 0.01724 Ω·mm²/m) by the area

      R/m=0.017242.8=0.00615714 Ω/m
    2. Change the length to meters to match the resistance per meter (1 ft = 0.3048 m)

      90 ft×0.3048=27.432 m
    3. Three-phase drop between two lines: multiply √3 × length × resistance per meter × current

      Vd=3×27.432×0.00615714×14=4.095674 V
    4. Divide the drop by the source voltage to see what share of it is lost, as a percent

      4.095674134×100=3.0565%
    5. Take the drop away from the source voltage to get what is left at the load

      134−4.095674=129.904326 V
  8. 8. Voltage drop: 6.57 V

    1. Resistance per meter of copper at 20 °C: divide the metal's resistivity ρ (how strongly it resists current, 1.724e-8 Ω·m or 0.01724 Ω·mm²/m) by the area

      R/m=0.017242.4=0.00718333 Ω/m
    2. Change the length to meters to match the resistance per meter (1 ft = 0.3048 m)

      125 ft×0.3048=38.1 m
    3. The current flows out and back, so the drop covers twice the one-way length: 2 × length × resistance per meter × current

      Vd=2×38.1×0.00718333×12=6.56844 V
    4. Divide the drop by the source voltage to see what share of it is lost, as a percent

      6.56844145×100=4.53%
    5. Take the drop away from the source voltage to get what is left at the load

      145−6.56844=138.43156 V
  9. 9. Voltage drop: 8.99 V

    1. Resistance per meter of copper at 20 °C: divide the metal's resistivity ρ (how strongly it resists current, 1.724e-8 Ω·m or 0.01724 Ω·mm²/m) by the area

      R/m=0.017241.8=0.00957778 Ω/m
    2. Change the length to meters to match the resistance per meter (1 ft = 0.3048 m)

      110 ft×0.3048=33.528 m
    3. The current flows out and back, so the drop covers twice the one-way length: 2 × length × resistance per meter × current

      Vd=2×33.528×0.00957778×14=8.991465 V
    4. Divide the drop by the source voltage to see what share of it is lost, as a percent

      8.991465125×100=7.1932%
    5. Take the drop away from the source voltage to get what is left at the load

      125−8.991465=116.008535 V
  10. 10. Voltage drop: 5.93 V

    1. Find the wire's thickness (diameter d) from its gauge number n = 11, using the standard AWG formula

      d=0.127×92(36−1139)=2.304847 mm
    2. Work out the area of the round wire's cut end (A). A bigger area means less resistance

      A=π4×2.3048472=4.172286 mm²
    3. Resistance per meter of aluminum at 20 °C: divide the metal's resistivity ρ (how strongly it resists current, 2.82e-8 Ω·m or 0.0282 Ω·mm²/m) by the area

      R/m=0.02824.172286=0.00675889 Ω/m
    4. Change the length to meters to match the resistance per meter (1 ft = 0.3048 m)

      120 ft×0.3048=36.576 m
    5. The current flows out and back, so the drop covers twice the one-way length: 2 × length × resistance per meter × current

      Vd=2×36.576×0.00675889×12=5.933112 V
    6. Divide the drop by the source voltage to see what share of it is lost, as a percent

      5.933112130×100=4.5639%
    7. Take the drop away from the source voltage to get what is left at the load

      130−5.933112=124.066888 V