What this calculator does
Get a first estimate of what size wire a job needs. Enter the current, the voltage, the distance and how much voltage you can afford to lose. You'll get a suggested copper or aluminum size in AWG (American Wire Gauge).
This is a planning estimate, not an approved design. It doesn't show that a job meets any code. Local code and a licensed electrician decide what actually gets installed.
Where it's used
Why this math matters outside the classroom:
- Detached garage planning. A homeowner planning a 30 A, 240 V feed over 150 feet sees an estimate of 8 AWG copper before calling an electrician.
- RV and solar runs. A DIY planner sees how a 12 V circuit needs much larger wire than a 240 V one over the same distance.
- Material pricing. An estimator compares copper and aluminum sizes for a 100-foot feeder before asking an electrician for a quote.
- Physics class. A student sees how doubling a run's length doubles the voltage drop, from 1.2% to 2.4%.
How to use it
- Choose copper or aluminum and the type of circuit.
- Enter the load current and the source voltage.
- Enter the one-way distance from the source to the load.
- Enter the voltage drop you'll allow, then read the suggested size and the table.
What the inputs mean
- Load current
- Use the full load. Loads that run for hours may need extra margin, so ask your electrician how to treat them.
- One-way distance
- Enter the one-way distance. The calculator accounts for the return path itself.
- Allowed voltage drop
- Voltage drop is the voltage lost along the wire. Too much can make motors run hot and lights run dim. A target of 3% is a common rule of thumb.
Formula and method
DC and single-phase drop = 2 × L × R × I three-phase drop = √3 × L × R × I drop % = drop ÷ V × 100 size = smallest wire that passes both checks
L is the one-way length, R is the wire's resistance per unit of length, I is the current and V is the source voltage. Thicker wire has lower resistance, so it loses less voltage.
The calculator runs two checks. First, the wire must carry the current without overheating. For that, it uses the 75 °C column of NEC Table 310.16, which is the US electrical code's main ampacity table. Ampacity means how many amps a wire can safely carry.
That column assumes no more than three current-carrying wires together and air at 30 °C (86 °F). Sizes 14, 12 and 10 AWG also have lower limits for circuit protection, and the calculator uses those. Second, the voltage drop must stay within your limit.
Worked example
You need to feed a 30 A load at 240 V, single-phase, 150 feet away, with copper wire and a 3% limit.
- The table limits point to 10 AWG for 30 A.
- At 150 feet, 10 AWG would lose 3.75%, which is over your limit.
- The next size up, 8 AWG, loses 2.36%, which is within your limit.
Result: The planning estimate is 8 AWG copper. Local code and a licensed electrician decide the final size.
Understanding the result
If the size is larger than the one needed for current alone, voltage drop is the reason. That's common on long runs and at low voltages such as 12 V.
The table under the result shows every size for your run. That helps when you're comparing cost against a lower drop.
Assumptions and limitations
- Ampacity comes from the 75 °C column of NEC Table 310.16, as reproduced in published charts. We did not read the NFPA text itself.
- Resistance is the DC value of a solid round wire at 20 °C. Hot or stranded wire resists a little more, so real drop can be higher.
- Inductance and power factor are left out of AC circuits.
- This is never a statement that a design meets code. Local rules and code editions differ.
- It doesn't adjust for hot locations, bundled wires, insulation type, terminal ratings, conduit fill or long-running loads. Any of these can require a larger wire.
- It doesn't choose breakers, and it isn't for motors, welders or air conditioners, which have their own rules.
- Electrical work can be dangerous. Have a licensed electrician design and inspect it.
Frequently asked questions
Is the size here code-compliant?
We can't say that, and you shouldn't assume it. It's a planning estimate. Local code and a licensed electrician decide.
Why does 14 AWG show 20 A but use 15 A?
The table lists 20 A in this column, but a separate rule for small wires limits circuit protection. So the calculator plans with the lower 15 A figure.
Why is aluminum larger than copper?
Aluminum resists current more than copper does. So it needs a thicker wire to carry the same current.
Which distance do I enter?
Enter the one-way distance. For a load 150 feet away, enter 150 and not 300.
Sources
- Allowable ampacities of insulated conductors (Table 310-16 reproduction) (checked 2026-10-31)
- Wire ampacity chart, NEC 310.16 copper and aluminum (checked 2026-10-31)
- Small conductor rules and protection limits, NEC 240.4(D) (checked 2026-10-31)
How this calculator is checked
Method: NEC Table 310.16 75 °C values as reproduced by Turn2Engineering (cites NFPA 70 2026) and Border States (1996 table), which agree for sizes 12 AWG to 4/0; 14 AWG from Turn2Engineering. Small-conductor limits from an NEC 240.4(D) study guide. The NFPA text was not read. Drop model is shared with voltage-drop. The calculation is covered by automated tests with known reference values and edge cases. Last updated 2026-10-31. Found a problem? Tell us.