Name Date
Wire Size worksheet
Grades 9–10
Calcapedia Solve each problem and show your work. Round answers to 2 decimal places where needed.
- 1.
Problem 1. - Conductor: Aluminum
- Circuit type: DC
- Load current: 50 A
- Source voltage: 480 V
- One-way distance: 180 ft
- Allowed voltage drop: 3%
Find: Suggested size (planning estimate)
Answer
- 2.
Problem 2. - Conductor: Copper
- Circuit type: Three-phase AC
- Load current: 30 A
- Source voltage: 24 V
- One-way distance: 130 ft
- Allowed voltage drop: 2%
Find: Suggested size (planning estimate)
Answer
- 3.
Problem 3. - Conductor: Copper
- Circuit type: Single-phase AC
- Load current: 50 A
- Source voltage: 277 V
- One-way distance: 140 ft
- Allowed voltage drop: 5%
Find: Suggested size (planning estimate)
Answer
- 4.
Problem 4. - Conductor: Copper
- Circuit type: Three-phase AC
- Load current: 20 A
- Source voltage: 48 V
- One-way distance: 120 ft
- Allowed voltage drop: 3%
Find: Suggested size (planning estimate)
Answer
- 5.
Problem 5. - Conductor: Copper
- Circuit type: DC
- Load current: 15 A
- Source voltage: 208 V
- One-way distance: 180 ft
- Allowed voltage drop: 3%
Find: Suggested size (planning estimate)
Answer
- 6.
Problem 6. - Conductor: Copper
- Circuit type: Three-phase AC
- Load current: 100 A
- Source voltage: 480 V
- One-way distance: 200 ft
- Allowed voltage drop: 2%
Find: Suggested size (planning estimate)
Answer
- 7.
Problem 7. - Conductor: Copper
- Circuit type: Three-phase AC
- Load current: 30 A
- Source voltage: 480 V
- One-way distance: 190 ft
- Allowed voltage drop: 5%
Find: Suggested size (planning estimate)
Answer
- 8.
Problem 8. - Conductor: Aluminum
- Circuit type: Single-phase AC
- Load current: 15 A
- Source voltage: 277 V
- One-way distance: 140 ft
- Allowed voltage drop: 5%
Find: Suggested size (planning estimate)
Answer
- 9.
Problem 9. - Conductor: Copper
- Circuit type: DC
- Load current: 60 A
- Source voltage: 208 V
- One-way distance: 104 ft
- Allowed voltage drop: 2%
Find: Suggested size (planning estimate)
Answer
- 10.
Problem 10. - Conductor: Aluminum
- Circuit type: Single-phase AC
- Load current: 15 A
- Source voltage: 208 V
- One-way distance: 150 ft
- Allowed voltage drop: 5%
Find: Suggested size (planning estimate)
Answer
Answer key: Wire Size worksheet
Calcapedia 1. Suggested size (planning estimate): 6 AWG aluminum
Find the smallest size the table allows for 50 A, using the 75 °C column and the limits for small wires
Work out the resistance of 6 AWG wire over the run. Current travels out and back, so double the one-way length
Multiply by the current to get the voltage lost in the wire
Compare that loss with your source voltage to see the percent drop
Current sets the size here. Voltage drop is already within your limit.
2. Suggested size (planning estimate): 3/0 AWG copper
Find the smallest size the table allows for 30 A, using the 75 °C column and the limits for small wires
Work out the resistance of 3/0 AWG wire over the run. Three-phase circuits use √3 times the one-way length
Multiply by the current to get the voltage lost in the wire
Compare that loss with your source voltage to see the percent drop
Voltage drop sets the size here. 10 AWG could carry the current, but it would lose 28.11%.
3. Suggested size (planning estimate): 8 AWG copper
Find the smallest size the table allows for 50 A, using the 75 °C column and the limits for small wires
Work out the resistance of 8 AWG wire over the run. Current travels out and back, so double the one-way length
Multiply by the current to get the voltage lost in the wire
Compare that loss with your source voltage to see the percent drop
Current sets the size here. Voltage drop is already within your limit.
4. Suggested size (planning estimate): 4 AWG copper
Find the smallest size the table allows for 20 A, using the 75 °C column and the limits for small wires
Work out the resistance of 4 AWG wire over the run. Three-phase circuits use √3 times the one-way length
Multiply by the current to get the voltage lost in the wire
Compare that loss with your source voltage to see the percent drop
Voltage drop sets the size here. 12 AWG could carry the current, but it would lose 13.75%.
5. Suggested size (planning estimate): 10 AWG copper
Find the smallest size the table allows for 15 A, using the 75 °C column and the limits for small wires
Work out the resistance of 10 AWG wire over the run. Current travels out and back, so double the one-way length
Multiply by the current to get the voltage lost in the wire
Compare that loss with your source voltage to see the percent drop
Voltage drop sets the size here. 14 AWG could carry the current, but it would lose 6.56%.
6. Suggested size (planning estimate): 3 AWG copper
Find the smallest size the table allows for 100 A, using the 75 °C column and the limits for small wires
Work out the resistance of 3 AWG wire over the run. Three-phase circuits use √3 times the one-way length
Multiply by the current to get the voltage lost in the wire
Compare that loss with your source voltage to see the percent drop
Current sets the size here. Voltage drop is already within your limit.
7. Suggested size (planning estimate): 10 AWG copper
Find the smallest size the table allows for 30 A, using the 75 °C column and the limits for small wires
Work out the resistance of 10 AWG wire over the run. Three-phase circuits use √3 times the one-way length
Multiply by the current to get the voltage lost in the wire
Compare that loss with your source voltage to see the percent drop
Current sets the size here. Voltage drop is already within your limit.
8. Suggested size (planning estimate): 12 AWG aluminum
Find the smallest size the table allows for 15 A, using the 75 °C column and the limits for small wires
Work out the resistance of 12 AWG wire over the run. Current travels out and back, so double the one-way length
Multiply by the current to get the voltage lost in the wire
Compare that loss with your source voltage to see the percent drop
Current sets the size here. Voltage drop is already within your limit.
9. Suggested size (planning estimate): 4 AWG copper
Find the smallest size the table allows for 60 A, using the 75 °C column and the limits for small wires
Work out the resistance of 4 AWG wire over the run. Current travels out and back, so double the one-way length
Multiply by the current to get the voltage lost in the wire
Compare that loss with your source voltage to see the percent drop
Voltage drop sets the size here. 6 AWG could carry the current, but it would lose 2.37%.
10. Suggested size (planning estimate): 10 AWG aluminum
Find the smallest size the table allows for 15 A, using the 75 °C column and the limits for small wires
Work out the resistance of 10 AWG wire over the run. Current travels out and back, so double the one-way length
Multiply by the current to get the voltage lost in the wire
Compare that loss with your source voltage to see the percent drop
Voltage drop sets the size here. 12 AWG could carry the current, but it would lose 5.62%.